ELE07-03049
| Electrical Rough-In | 8/30/2007 | 8/31/2007 | 8/31/2007 2:25:17 PM | P | FAIL |
|
|
james ###-#### called open grd , on grded system
|
ELE07-02850
| Electrical Rough-In | 8/31/2007 | 8/31/2007 | 8/31/2007 1:43:13 PM | P | PASS |
|
|
kitchen; Jared; call hour prior; Phone #: ###-#### Internet Inspection Request from: Hattie James kit r/i ok
|
ELE07-02081
| Final | 8/31/2007 | 8/31/2007 | 8/31/2007 1:09:21 PM | P | FAIL |
|
|
wayne; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt corr called 250.148 grd all metal boxes , 314.16 box fill handy box furnace, 408.4 panel schedule be specific purpose and use
|
ELE07-02972
| Electrical Rough-In | 8/31/2007 | 8/31/2007 | 8/31/2007 12:35:00 PM | P | FAIL |
|
|
Tim; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt u/g ok still needs back-fed breaker device called
|
ELE07-02699
| Final | 8/30/2007 | 8/31/2007 | 8/31/2007 11:00:15 AM | A | PASS |
|
|
reinspect; Jeff; Phone #: ###-#### Internet Inspection Request from: Hattie James ok
|
ELE07-02294
| Electrical Rough-In | 8/29/2007 | 8/31/2007 | 8/31/2007 10:36:10 AM | A | FAIL |
|
|
This will be for a rough-in wall inspection please. Steve Berry will be the contact person. Thank you and have a great day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw corr met contr box fill nail plates 11/4"outlet spacing replace 2,3,4 gang boxes with broken clamps, 314.29 boxes not accessible in trusses needs #$ to bond water free length short grd wires, BCC no violations retained hot tub
|
ELE07-02346
| Permanent Service | 8/31/2007 | 8/31/2007 | 8/31/2007 9:34:14 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 8/31/2007 at 7:15:36 AM. Contact: ###-####. corr. 250.8 no SMS for grds or bonds, grd to concrete encased electrode , grd or bond water size too table 250.66
|
ELE07-02972
| Electrical Rough-In | 8/30/2007 | 8/31/2007 | 8/31/2007 9:05:09 AM | A | FAIL |
|
|
Tim; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt corr 110.26(F)(1( clearence for panel, 300.4(A)(1)&(D) nail plates inside outside edges the same for cables parallel to framing members, 408.36(F) shall install back-fed device for main breaker 250.64(E) or 312.5 needs metal conn listed for grding or plastic conn. for GEC called
|
ELE07-02864
| Electrical Rough-In | 8/30/2007 | 8/31/2007 | 8/31/2007 8:38:09 AM | A | PASS |
|
|
Call before arrival Phone #: ###-#### Internet Inspection Request from: Joe Thomas r/i ok corr made
|
ELE06-03281
| Final | 8/30/2007 | 8/31/2007 | 8/31/2007 8:19:46 AM | A | PASS |
|
|
Please inspect final for A and B wings. Phone #: ###-#### Internet Inspection Request from: Jim Friend ok card signed
|
ELE06-03280
| Final | 8/30/2007 | 8/31/2007 | 8/31/2007 8:19:22 AM | A | PASS |
|
|
Please inspect final for D wing. Phone #: ###-#### Internet Inspection Request from: Jim Friend ok card signed
|
ELE06-02704
| Final | 8/30/2007 | 8/31/2007 | 8/31/2007 8:18:57 AM | A | PASS |
|
|
Please inspect finals for C wing. Phone #: ###-#### Internet Inspection Request from: Jim Friend ok card signed
|