Inspections for the day of: Friday, August 31, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-03049 Electrical Rough-In8/30/20078/31/20078/31/2007 2:25:17 PMPFAIL
james ###-#### called open grd , on grded system
ELE07-02850 Electrical Rough-In8/31/20078/31/20078/31/2007 1:43:13 PMPPASS
kitchen; Jared; call hour prior; Phone #: ###-#### Internet Inspection Request from: Hattie James kit r/i ok
ELE07-02081 Final8/31/20078/31/20078/31/2007 1:09:21 PMPFAIL
wayne; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt
corr called 250.148 grd all metal boxes , 314.16 box fill handy box furnace, 408.4 panel schedule be specific purpose and use
ELE07-02972 Electrical Rough-In8/31/20078/31/20078/31/2007 12:35:00 PMPFAIL
Tim; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt u/g ok still needs back-fed breaker device called
ELE07-02699 Final8/30/20078/31/20078/31/2007 11:00:15 AMAPASS
reinspect; Jeff; Phone #: ###-#### Internet Inspection Request from: Hattie James ok
ELE07-02294 Electrical Rough-In8/29/20078/31/20078/31/2007 10:36:10 AMAFAIL
This will be for a rough-in wall inspection please. Steve Berry will be the contact person. Thank you and have a great day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw corr met contr box fill nail plates 11/4"outlet spacing replace 2,3,4 gang boxes with broken clamps, 314.29 boxes not accessible in trusses needs #$ to bond water free length short grd wires, BCC no violations retained hot tub
ELE07-02346 Permanent Service8/31/20078/31/20078/31/2007 9:34:14 AMAFAIL
Scheduled by a contractor via Hello! on 8/31/2007 at 7:15:36 AM. Contact: ###-####. corr. 250.8 no SMS for grds or bonds, grd to concrete encased electrode , grd or bond water size too table 250.66
ELE07-02972 Electrical Rough-In8/30/20078/31/20078/31/2007 9:05:09 AMAFAIL
Tim; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt corr 110.26(F)(1( clearence for panel, 300.4(A)(1)&(D) nail plates inside outside edges the same for cables parallel to framing members, 408.36(F) shall install back-fed device for main breaker 250.64(E) or 312.5 needs metal conn listed for grding or plastic conn. for GEC called
ELE07-02864 Electrical Rough-In8/30/20078/31/20078/31/2007 8:38:09 AMAPASS
Call before arrival Phone #: ###-#### Internet Inspection Request from: Joe Thomas r/i ok corr made
ELE06-03281 Final8/30/20078/31/20078/31/2007 8:19:46 AMAPASS
Please inspect final for A and B wings. Phone #: ###-#### Internet Inspection Request from: Jim Friend ok card signed
ELE06-03280 Final8/30/20078/31/20078/31/2007 8:19:22 AMAPASS
Please inspect final for D wing. Phone #: ###-#### Internet Inspection Request from: Jim Friend ok card signed
ELE06-02704 Final8/30/20078/31/20078/31/2007 8:18:57 AMAPASS
Please inspect finals for C wing. Phone #: ###-#### Internet Inspection Request from: Jim Friend ok card signed