FIR07-00598
| INSP-Final Inspection | 8/31/2007 | 8/31/2007 | 8/31/2007 3:32:37 PM | P | FAIL |
|
|
This project is not ready for a final due to the approved drawings not being available on site. The sprinkler piping at the old connecting walkway is ok to cover.
|
BLD07-02377
| FIRE-Final Inspection | 8/31/2007 | 8/31/2007 | 8/31/2007 2:51:16 PM | P | FAIL |
|
|
Repair the emergency lights in the kitchen.
|
FIR05-00536
| INSP-Final Inspection | 8/31/2007 | 8/31/2007 | 8/31/2007 2:49:57 PM | P | CANC |
|
|
See inspection request for this morning for inspection notes.
|
FIR06-00011
| INSP-Alarm Testing | 8/30/2007 | 8/31/2007 | 8/31/2007 2:19:42 PM | P | DONE |
|
|
I tested the firemans phone for functionality from the penthouse to the fourth floor. One phone jack is missing on the 9th floor and we missed testing one in the elevator equipment room.
|
BLD07-00913
| FIRE-Final Inspection | 8/30/2007 | 8/31/2007 | 8/31/2007 2:17:56 PM | A | FAIL |
|
|
See the front page of the city approved plans for the correction list. They include the installation of the exit sign in the east portion of the building, foam covers for the duct detector sample tubes, a map at the facp, move the address as per the plans, provide the "Inspectors Test" sign and reduce the storage in the warehouse.
|
BLD07-01201
| FIRE-Final Inspection | 8/30/2007 | 8/31/2007 | 8/31/2007 2:14:18 PM | A | PART |
|
|
Tenant space 10464 is ok to cover. The second tenant space did not have all of the insulation backing held to the roof deck as agreed.
|
FIR07-00479
| INSP-Sprinkler Rough-in | 8/30/2007 | 8/31/2007 | 8/31/2007 2:10:23 PM | A | PASS |
|
|
The remaining exposed piping is ok to cover. The contractor owes me an as-built plan as per the scope of work. After canopies and ceiling tile have been verified this project can be finaled
|
FIR05-00536
| INSP-Final Inspection | 8/30/2007 | 8/31/2007 | 8/31/2007 12:39:28 PM | A | FAIL |
|
|
There are many rooms that are missing ceiling tile and are locked with no access to inspect. Project was not ready for inspection.
|
FIR06-00813
| INSP-Conference | 8/29/2007 | 8/31/2007 | 8/31/2007 12:24:17 PM | A | DONE |
|
|
The fire alarm contractor wanted to know the specifics of why I can't dedicate specific times to show up and spend doing their inspection.
|
BLD07-01969
| FIRE-Final Inspection | 8/30/2007 | 8/31/2007 | 8/31/2007 11:36:27 AM | A | FAIL |
|
|
Repair the exit signs and emergency light including the exit corridor at the restrooms.
|
BLD06-00714
| FIRE-Final Inspection | 8/30/2007 | 8/31/2007 | 8/31/2007 11:10:59 AM | A | PART |
|
|
This inspection was for 5237 only. It is ok with me to occupy. No signature was given since the scope of work was for four condo's.
|
FIR07-00539
| INSP-Alarm Testing | 8/30/2007 | 8/31/2007 | 8/31/2007 11:08:09 AM | A | PASS |
|
|
Permit finaled
|
FIR07-00642
| INSP-Sprinkler Rough-in | 8/30/2007 | 8/31/2007 | 8/31/2007 8:11:17 AM | A | PASS |
|
|
This rough to cover is for areas 7&8. Piping is ok to cover. See the city approved plans for the location with todays date.
|