FIR06-00379
| INSP-Final Inspection | 8/28/2009 | 8/31/2009 | 8/31/2009 5:19:30 PM | P | FAIL |
|
|
Area under stairs at the lower level is missing coverage, pendent head at the riser is blocked by an adjacent soffit, riser and DCVA are three years overdue annual inspection. Outside bell tested okay, flow switch operated.
|
FIR09-00485
| INSP-Sprinkler Rough-in/Hydro | 8/31/2009 | 8/31/2009 | 8/31/2009 5:15:14 PM | P | PART |
|
|
Overhead hydrostatic test completed satisfactory.
|
FIR09-00486
| INSP-Supply line flush | 8/28/2009 | 8/31/2009 | 8/31/2009 5:14:12 PM | A | PART |
|
|
UG fire supply line ductile riser and stub out to the first 90 are approved for bury- see annotations and initials on stamped plan set.
|
BLD09-01406
| FIRE-Final Inspection | 8/31/2009 | 8/31/2009 | 8/31/2009 5:05:28 PM | A | FAIL |
|
|
See correction notice on site for listed deficiency and associated IFC code sections for applicable requirements.
|