Inspections for the day of: Tuesday, August 31, 2010.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-02032 FIRE-Final Inspection8/31/20108/31/20109/1/2010 9:11:15 AMPPASS
Life safety passed
BLD10-01273 FIRE-Final Inspection8/31/20108/31/20108/31/2010 3:26:13 PMPFAIL
Need verification that the two existing fire doors that provide the separation between the two warehouses are operational. Ceritification from a door company is acceptable. They appear to have been hit by the fork lifts.
FIR10-00421 INSP-Final Inspection8/31/20108/31/20108/31/2010 3:11:49 PMPPASS
Permit finaled.
FIR10-00409 INSP-Final Inspection8/30/20108/31/20108/31/2010 2:58:15 PMPFAIL
Two heads as discussed need to have separate supplies from the branchline since the area does not appear to qualify for "Room Design" method of hydraulic calculations. I also noted that one pendant head in the office area is located too close to a wall and will need to be relocated as well as missing canopies provided. The fire sprinkler system has not been inspected for 10 years.
BLD10-01582 FIRE-Conference8/31/20108/31/20108/31/2010 2:53:05 PMPDONE
I met Bob Hosack on site while performing a sprinkler inspection. While performing the sprinkler inspection I found that an AES fire alarm transmitter had been installed without permits. I notified Bob that I would hold up the occupancy of the new tenant until this new fire alarm work had been permited, issued and passed a final inspection. I also found that the fire sprinkler system had not been inspected in ten years and I let Bob know that would also need to be addressed. I noted that one sprinkler pendant in the office area was located too close to a wall and would need to be relocated.
BLD10-00198 FIRE-Final Inspection8/30/20108/31/20108/31/2010 2:45:41 PMACANC
Cancel per wes Phone #: ###-####
FIR10-00369 INSP-Final Inspection8/30/20108/31/20108/31/2010 2:44:25 PMACANC
Cancel per wes Phone #: ###-####
BLD10-01994 FIRE-Final Inspection8/27/20108/31/20108/31/2010 1:02:50 PMAFAIL
- Provide one 2a,10bc fire extinguisher with current inspection tag mounted in a normal path of travel, repair the exit signs, test emergency lighting and repair if needed, provide correct address, it appears that a second restroom is required under previously expired building permit.
BLD10-01391 FIRE-Final Inspection8/30/20108/31/20108/31/2010 11:51:26 AMACANC
Cancel per Mike
BLD10-02012 FIRE-Final Inspection8/31/20108/31/20108/31/2010 10:46:11 AMPPASS
Life safety passed.
FIR10-00224 INSP-Final Inspection8/30/20108/31/20108/31/2010 10:45:44 AMAFAIL
Permit finaled. The zone had to be changed from an alarm to a supervisory as we waited.
BLD10-00688 FIRE-Final Inspection8/27/20108/31/20108/31/2010 9:21:04 AMAPASS
life safety passed
FIR10-00330 INSP-Final Inspection8/30/20108/31/20108/31/2010 9:06:14 AMAPASS
Permit passed.