BLD09-02032
| FIRE-Final Inspection | 8/31/2010 | 8/31/2010 | 9/1/2010 9:11:15 AM | P | PASS |
|
|
Life safety passed
|
BLD10-01273
| FIRE-Final Inspection | 8/31/2010 | 8/31/2010 | 8/31/2010 3:26:13 PM | P | FAIL |
|
|
Need verification that the two existing fire doors that provide the separation between the two warehouses are operational. Ceritification from a door company is acceptable. They appear to have been hit by the fork lifts.
|
FIR10-00421
| INSP-Final Inspection | 8/31/2010 | 8/31/2010 | 8/31/2010 3:11:49 PM | P | PASS |
|
|
Permit finaled.
|
FIR10-00409
| INSP-Final Inspection | 8/30/2010 | 8/31/2010 | 8/31/2010 2:58:15 PM | P | FAIL |
|
|
Two heads as discussed need to have separate supplies from the branchline since the area does not appear to qualify for "Room Design" method of hydraulic calculations. I also noted that one pendant head in the office area is located too close to a wall and will need to be relocated as well as missing canopies provided. The fire sprinkler system has not been inspected for 10 years.
|
BLD10-01582
| FIRE-Conference | 8/31/2010 | 8/31/2010 | 8/31/2010 2:53:05 PM | P | DONE |
|
|
I met Bob Hosack on site while performing a sprinkler inspection. While performing the sprinkler inspection I found that an AES fire alarm transmitter had been installed without permits. I notified Bob that I would hold up the occupancy of the new tenant until this new fire alarm work had been permited, issued and passed a final inspection. I also found that the fire sprinkler system had not been inspected in ten years and I let Bob know that would also need to be addressed. I noted that one sprinkler pendant in the office area was located too close to a wall and would need to be relocated.
|
BLD10-00198
| FIRE-Final Inspection | 8/30/2010 | 8/31/2010 | 8/31/2010 2:45:41 PM | A | CANC |
|
|
Cancel per wes Phone #: ###-####
|
FIR10-00369
| INSP-Final Inspection | 8/30/2010 | 8/31/2010 | 8/31/2010 2:44:25 PM | A | CANC |
|
|
Cancel per wes Phone #: ###-####
|
BLD10-01994
| FIRE-Final Inspection | 8/27/2010 | 8/31/2010 | 8/31/2010 1:02:50 PM | A | FAIL |
|
|
- Provide one 2a,10bc fire extinguisher with current inspection tag mounted in a normal path of travel, repair the exit signs, test emergency lighting and repair if needed, provide correct address, it appears that a second restroom is required under previously expired building permit.
|
BLD10-01391
| FIRE-Final Inspection | 8/30/2010 | 8/31/2010 | 8/31/2010 11:51:26 AM | A | CANC |
|
|
Cancel per Mike
|
BLD10-02012
| FIRE-Final Inspection | 8/31/2010 | 8/31/2010 | 8/31/2010 10:46:11 AM | P | PASS |
|
|
Life safety passed.
|
FIR10-00224
| INSP-Final Inspection | 8/30/2010 | 8/31/2010 | 8/31/2010 10:45:44 AM | A | FAIL |
|
|
Permit finaled. The zone had to be changed from an alarm to a supervisory as we waited.
|
BLD10-00688
| FIRE-Final Inspection | 8/27/2010 | 8/31/2010 | 8/31/2010 9:21:04 AM | A | PASS |
|
|
life safety passed
|
FIR10-00330
| INSP-Final Inspection | 8/30/2010 | 8/31/2010 | 8/31/2010 9:06:14 AM | A | PASS |
|
|
Permit passed.
|