ELE11-00480
| Final | 8/31/2011 | 8/31/2011 | 8/31/2011 3:12:45 PM | P | PASS |
|
|
ok
|
ELE11-00819
| Final | 8/31/2011 | 8/31/2011 | 8/31/2011 3:12:34 PM | P | PASS |
|
|
ok
|
ELE11-00631
| Final | 8/31/2011 | 8/31/2011 | 8/31/2011 3:12:23 PM | P | PASS |
|
|
|
ELE11-01668
| Final | 8/31/2011 | 8/31/2011 | 8/31/2011 3:10:35 PM | P | PASS |
|
|
mike Phone #: ###-#### ok card signed
|
ELE11-01681
| Electrical Rough-In | 8/31/2011 | 8/31/2011 | 8/31/2011 3:10:02 PM | P | PASS |
|
|
r/i for all of the grid ceiling ok
|
ELE11-01681
| Final | 8/31/2011 | 8/31/2011 | 8/31/2011 3:05:56 PM | P | NR |
|
|
meet tom 12:01pm today Phone #: ###-#### >> Inspection requested via web by mike brown see added r/i
|
ELE11-01988
| Rough-In Permanent Service | 8/30/2011 | 8/31/2011 | 8/31/2011 2:22:22 PM | P | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Brad Girard BCC needs 2" rigid or IMC mast, 250.64(C) GEC shall be continuous from u/g water pipe to service panel, 250.119 shall not ID #6 or smaller drop to garage,334.15 (B) shall use rigid, IMC, EMT, or PVC scedule 80 too protect romex in garage 250.56 grd rods shall be 6ft apart, make sure wire in masts are sunlight resistant called
|
ELE11-00479
| Final | 8/31/2011 | 8/31/2011 | 8/31/2011 12:55:16 PM | A | PASS |
|
|
sign
|
ELE11-00723
| Final | 8/31/2011 | 8/31/2011 | 8/31/2011 12:55:03 PM | A | PASS |
|
|
sign
|
ELE11-00790
| Final | 8/31/2011 | 8/31/2011 | 8/31/2011 12:54:46 PM | A | CANC |
|
|
waiting for hold to be removed
|
ELE11-01207
| Final | 8/31/2011 | 8/31/2011 | 8/31/2011 12:54:32 PM | A | PASS |
|
|
sign
|
ELE11-01974
| Electrical Rough-In | 8/30/2011 | 8/31/2011 | 8/31/2011 10:19:52 AM | A | PASS |
|
|
door with green dot over lock is open. Looking for cover on walls that need sheet rock. White EMT bushings will be be installed on 1 1/2" data conduits. Phone #: ###-#### >> Inspection requested via web by Jim Snodgrass
|
ELE11-01255
| Final | 8/30/2011 | 8/31/2011 | 8/31/2011 10:19:35 AM | A | PASS |
|
|
final on new addition, any questions call Clint @ ###-#### Phone #: ###-#### >> Inspection requested via web by Andy Rose
|
ELE11-01630
| Final | 8/30/2011 | 8/31/2011 | 8/31/2011 10:19:08 AM | A | PASS |
|
|
Rochelle Phone #: ###-####
|