BLD11-00815
| FIRE-Final Inspection | 8/31/2011 | 8/31/2011 | 8/31/2011 3:36:09 PM | P | PASS |
|
|
life safety passed
|
FIR11-00376
| INSP-Final Inspection | 8/31/2011 | 8/31/2011 | 8/31/2011 3:18:42 PM | P | PASS |
|
|
Permit finaled. The hood suppresson system functioned correctly.
|
FIR11-00376
| INSP-Sprinkler Rough-in/Hydro | 8/31/2011 | 8/31/2011 | 8/31/2011 3:18:27 PM | P | PASS |
|
|
Permit finaled. The hood suppresson system functioned correctly.
|
FIR11-00399
| INSP-Conference | 8/31/2011 | 8/31/2011 | 8/31/2011 3:08:26 PM | P | DONE |
|
|
Performed site visit to determine placement of heat detectors and found that the city approved plans do not show the heat detectors spaced for "sloped" ceilings, "High" ceilings or spacing taking "beam construction" into account. The plans also do not reflect the existing fire sprinkler riser which includes two interior tamper switches, an exterior wall PIV and a flow switch. After a discussion with plan review it was determined that a plan modification/resubmittal is needed to show this information. This was relayed to the fire alarm tech.
|
BLD11-00101
| FIRE-Final Inspection | 8/30/2011 | 8/31/2011 | 8/31/2011 11:23:21 AM | A | PASS |
|
|
life safety passed
|
FIR11-00427
| INSP-Final Inspection | 8/30/2011 | 8/31/2011 | 8/31/2011 10:27:37 AM | P | PASS |
|
|
permit finaled
|
BLD09-01976
| FIRE-Final Inspection | 8/31/2011 | 8/31/2011 | 8/31/2011 10:23:38 AM | P | PASS |
|
|
life safety passed
|
FIR11-00339
| INSP-Final Inspection | 8/30/2011 | 8/31/2011 | 8/31/2011 8:56:09 AM | A | FAIL |
|
|
Request final inspection. Please call Javier to schedule inspection time. Thanks. Phone #: ###-####
Call contact twice and went to job site and found no one waiting. No inspection performed.
|