Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00405 INSP-Final Inspection8/30/20128/31/20129/4/2012 4:17:37 PMAFAIL
Noted eight locations where minimum distances to heat sources are not met per NFPA 13D 2010 table 7.5.5.3. Also noted mixed response types at one compartment in the lower level. Outside bell and flow test completed satisfactory.
BLD12-00550 FIRE-Final Inspection8/30/20128/31/20128/31/2012 5:06:48 PMPNH
Peter Phone #: ###-####
FIR11-00650 INSP-Final Inspection8/29/20128/31/20128/31/2012 4:52:48 PMANR
Pending corrections.
FIR12-00469 INSP-Sprinkler Rough-in8/30/20128/31/20128/31/2012 4:03:27 PMPPART
Okay to cover fire sprinkler work at the new entry vestibule and the womens restroom- see dated approved plan set annotations. Still need to verify insulation fill at the combustible concealed spaces- incomplete at this time.
BLD12-00764 FIRE-Final Inspection8/31/20128/31/20128/31/2012 3:48:22 PMPFAIL
Missing fire code review notes on site, noted several missing exit signs and EM lights, door hardware needs revised at three locations, project is not in condition for final fire life safety approval at this time.
FIR12-00462 INSP-Final Inspection8/30/20128/31/20128/31/2012 3:45:40 PMPFAIL
pat Phone #: ###-####
BLD11-01304 FIRE-Final Inspection8/31/20128/31/20128/31/2012 2:22:56 PMPPASS
Scope of work completed. Life safety passed.
BLD12-00851 FIRE-Final Inspection8/30/20128/31/20128/31/2012 2:21:37 PMAFAIL
Correction items include; adding missing exit sign shown per plan at the sales floor area, repair two non-functional exit signs, provide missing escutcheon, post PFE as discussed. Smoke evac test completed acceptable.
FIR03-00788 FIR-Aging Inspection8/31/20128/31/20128/31/2012 2:17:15 PM NR
FIR02-00268 FIR-Aging Inspection8/31/20128/31/20128/31/2012 2:16:51 PM DEFR
FIR03-00397 FIR-Aging Inspection8/31/20128/31/20128/31/2012 2:16:29 PM DEFR
FIR03-00411 FIR-Aging Inspection8/31/20128/31/20128/31/2012 2:15:22 PM DEFR
FIR03-00066 FIR-Aging Inspection8/31/20128/31/20128/31/2012 2:14:53 PM DEFR
FIR12-00247 INSP-Sprinkler Rough-in8/30/20128/31/20128/31/2012 2:14:32 PMAPART
UG fire supply lines including the IBR's at buildings 5, 6, and 7 are approved for bury- see clouded annotations with today's date on stamped plan set. Note* supply pipe route changes matching field modifications are included on the overhead plan set.
FIR12-00480 INSP-Final Inspection8/30/20128/31/20128/31/2012 2:09:32 PMAPASS
Hood suppression system operated correctly under test conditions. Permit finaled.
BLD11-01271 FIRE-Final Inspection8/30/20128/31/20128/31/2012 2:08:23 PMAPASS
Fire life safety inspection passed. Contractor to post max. occupant load signage per plan as discussed. PFE's posted where indicated.