Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00096 INSP-Sprinkler Rough-in8/31/20158/31/20158/31/2015 4:08:52 PMPPASS
Hydrostatic pressure test for the two new standpipes added on one sire of each (two) horizontal exits (south corridor and middle corridor)
200 psi @ 2 hours - PASSED
NOTE: Two new control valves supplying these new standpipes will have to be tied into the fire alarm system for monitoring purposes.