FIR15-00096
| INSP-Sprinkler Rough-in | 8/31/2015 | 8/31/2015 | 8/31/2015 4:08:52 PM | P | PASS |
|
|
Hydrostatic pressure test for the two new standpipes added on one sire of each (two) horizontal exits (south corridor and middle corridor) 200 psi @ 2 hours - PASSED NOTE: Two new control valves supplying these new standpipes will have to be tied into the fire alarm system for monitoring purposes.
|