Inspections for the day of: Thursday, August 31, 2017.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-02336 FIRE-Final Inspection8/31/20178/31/20178/31/2017 3:40:53 PMPPART
Fire sprinkler inspection for area called hase 1 complete (Northside of tenant space), no fire alarm modifications, fire extinguisher is now in place with a current inspection tag, exit discharge landing emergency lighting will be installed with phase 2 area. Life fire safety inspection for area called phase 1 passed/complete.
FIR17-00501 INSP-Sprinkler Rough-in8/31/20178/31/20178/31/2017 3:33:43 PMPPART
Rough to cover inspection for in building riser and stub out from the footing complete, area inspected approved for cover. Remaining underground to be installed at a later date.
BLD17-02336 FIRE-Final Inspection8/31/20178/31/20178/31/2017 11:20:29 AMPFAIL
Provide fire extinguisher on side that will be occupied, fire extinguisher must be tagged with a current inspection tag. City approved drawings show an existing exit sign above northeast exterior exit, door does not have exit sign or exterior exit discharge landing emergency lighting, provide exit sign above door with emergency lighting to include exit discharge landing.
BLD16-02417 FIRE-Final Inspection8/30/20178/31/20178/31/2017 10:39:52 AMACANC
Inspection for fire alarm permit not requested, life fire safety inspection cannot be completed until project related FIR permits are inspected and in the finaled status. This inspection request is cancelled.
FIR16-00774 INSP-Final Inspection8/30/20178/31/20178/31/2017 10:39:22 AMACANC
Fire sprinkler permit can be finaled after associated fire alarm components on fire sprinkler riser are completed with the fire alarm inspection. This inspection request is cancelled.
BLD17-03073 FIRE-Final Inspection8/30/20178/31/20178/31/2017 9:06:44 AMAPASS
No fire sprinklers, no fire alarms, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection passed/complete.
FIR17-00241 INSP-Final Inspection8/31/20178/31/20178/31/2017 8:25:28 AMPPASS
Final fire alarm inspection for demo work complete.
FIR17-00241 INSP-Alarm Testing8/30/20178/31/20178/31/2017 8:25:02 AMACANC
Dave Phone #: ###-####
FIR17-00270 INSP-Final Inspection8/30/20178/31/20178/31/2017 8:21:59 AMAPASS
Final fire alarm inspection for demo work complete.
BLD17-01359 FIRE-Final Inspection8/30/20178/31/20178/31/2017 7:14:12 AMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection for area of work passed/complete.
FIR17-00373 INSP-Final Inspection8/31/20178/31/20178/31/2017 7:12:59 AMAPASS
Final fire alarm inspection for area of work passed/complete.