Inspections for the day of: Friday, August 31, 2018.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-03163 Final8/31/20188/31/20188/31/2018 5:03:01 PMPPASS
AC unit to have seperate permit. Bushing installed. Final ok
ELE18-02662 Electrical Rough-In8/30/20188/31/20188/31/2018 4:57:20 PMPFAIL
Ceiling Phone #: ###-#### Inspection requested via web by steve ragan
300.15- All cables shall terminate in a box. 12-2 mc stubbed out of wall in a office.
314 25- Several box covers missing through out. KO seals needed.
ELE18-03320 Electrical Rough-In8/31/20188/31/20188/31/2018 4:15:01 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Level 3 perimeter walls only rough in ok cover
ELE18-00869 Electrical Rough-In8/31/20188/31/20188/31/2018 3:43:21 PMPPASS
UG cover. Danny is onsite Phone #: ###-#### Inspection requested via web by Buster Bowen Underground on eastside along back to center of complex rough in ok cover
ELE18-03324 Rough-In Permanent Service8/31/20188/31/20188/31/2018 3:14:05 PMPPASS
Call with any questions. Thank you Phone #: ###-#### Inspection requested via web by kim grundhauser
408.3(A)(2)- Barriers shall be in place to prevent inadvertant contact for final.
Rough in ok cover p/s u/g n ok
ELE18-03163 Final8/31/20188/31/20188/31/2018 2:09:02 PMPFAIL
200 amp existing pedestal Phone #: ###-#### Inspection requested via web by jamie berg
300.4(G)- Conduits containing #4 or larger conductors shall have a bushing installed to protect conductors from damage. 2" at pedistal.
334.12(B)(4)- NM cable shall not be installed in a wet or damp location. AC sitting on lot with 10-2 NM cable installed in flexible conduit to AC unit.
ELE18-03163 Permanent Service8/31/20188/31/20188/31/2018 2:08:49 PMPPASS
200 amp existing pedestal Phone #: ###-#### Inspection requested via web by jamie berg p/s u/g rec ok
ELE18-01757 Final8/31/20188/31/20188/31/2018 1:16:41 PMPPASS
garage code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
ELE18-03343 Temporary Service8/31/20188/31/20188/31/2018 12:53:32 PMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
ELE18-03316 Electrical Rough-In8/31/20188/31/20188/31/2018 12:19:42 PMAPASS
House is wired for outside lights. Wire is on soffit. When owner decides what light we will use cut in box for exact location. Phone #: ###-#### Inspection requested via web by Jason Wicks
Service change is planned. Loose wires to terminate in new panel. Rough in ok cover
ELE18-03329 Final8/30/20188/31/20188/31/2018 12:08:46 PMAPASS
Please give a call when on way ###-#### Phone #: ###-#### Inspection requested via web by Same Electric
GFCI protected. Final ok
ELE18-03329 Electrical Rough-In8/31/20188/31/20188/31/2018 12:08:32 PMPPASS
Please give a call when on way ###-#### Phone #: ###-#### Inspection requested via web by Same Electric
Added circuit for wall heater in master bathroom. Rough in ok
ELE18-02584 Electrical Rough-In8/30/20188/31/20188/31/2018 11:47:51 AMAPASS
Ceiling Inspection for cover.
Contact Jon Novak
Thank you Phone #: ###-#### Inspection requested via web by Tom Betty
Grid rough in ok cover
ELE18-03344 Conference8/31/20188/31/20188/31/2018 11:31:49 AMADONE
Need conference with owner and Idaho Power at 10am if you can make it. Please let me know. Phone #: ###-#### Inspection requested via web by Tom Jenkins
Discussed options to refeed service after service change. From Idaho Power vault into basement electrical room. With room all concrete with steel fire door ok to LB and pipe down inside room to allow electrtical equipment to legal height. Setting CT can and main disconnect and gear to refeed building loads. Door to electrical room to open out and have panic hardware installed. East portion of building to be fed seperately and shall have seperate service due to seperate address and seperated by firewall.
ELE18-03312 Rough-In Permanent Service8/29/20188/31/20188/31/2018 9:38:18 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
Rough in ok cover p/s u/g n ok
ELE18-03342 Temporary Service8/31/20188/31/20188/31/2018 9:19:04 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
ELE18-03006 Final8/30/20188/31/20188/31/2018 9:11:21 AMANR
garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk
Future requests for this lot if not ready will result in a reinspection fee. House has just been taped, no trim work done at this time.