Inspections for the day of: Wednesday, August 4, 2004.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00380 INSP-Final Inspection8/4/20048/4/20048/4/2004 12:00:00 AMAPASS
Fire alarm permit finaled 8/4/2004 11:48:12 AM
FIR04-00370 INSP-Final Inspection8/4/20048/4/20048/4/2004 12:00:00 AMAPASS
Fire sprinkler permit finaled
BLD04-00705 FIRE-Final Inspection8/4/20048/4/20048/4/2004 12:00:00 AMAFAIL
Provide one fire extinguisher per the fire review notes and provide "No Parking-Fire Lane" verbage on the red curbing at the new addition
BLD03-02891 FIRE-Conference8/4/20048/4/20048/4/2004 12:00:00 AMPDONE
A duct smoke detector is to be added to RTU8 8/4/2004 4:27:18 PM
FIR03-00012 INSP-Alarm Testing8/3/20048/4/20048/4/2004 12:00:00 AMPFAIL
Provide resubmittals showing the correct wiring for initiating zones and show door hold opens. Provide "Request to Exit" buttons per IFC 1003.3.1.3.4. See review notes. Provide correct count of horns. Provide verification of note #9. Need to retest pull stations and fire sprinkler items and horns on second floor. A re-inspection fee will apply upon the next inspection. 8/4/2004 4:25:07 PM