Inspections for the day of: Thursday, August 4, 2005.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-00732 Final8/4/20058/4/20058/4/2005 4:26:51 PMPCANC
richard; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called electrical contractor he is ok but general needs to get his building permits squared away so I can sign the right card for the job
ELE05-02821 Permanent Service8/3/20058/4/20058/4/2005 3:38:28 PMAFAIL
ROWDY ###-####///ASAP PLEASE cor. posted met contractor, told him on 08-03-05 what was required for working space,, 110.26 (A)thur(F) dedicated space
ELE05-02832 Rough-In Permanent Service8/4/20058/4/20058/4/2005 3:06:08 PMPPASS
rick ###-#### r/i ok called rick about outlet for fixed panel of back slider
p/s u/g new ok
ELE05-02819 Conference8/3/20058/4/20058/4/2005 2:09:56 PMPDONE
james ###-#### ok
ELE05-01404 Permanent Service8/4/20058/4/20058/4/2005 1:23:16 PMPPASS
eric; Phone #: ###-#### Internet Inspection Request from: Barbara Moore p/s u/g new ok
ELE05-02686 Final8/4/20058/4/20058/4/2005 12:43:10 PMPNR
yanke energy//please call with results at ###-#### kevin; Phone #: ###-#### Internet Inspection Request from: Barbara Moore no power yet could not final called
ELE05-01763 Final8/3/20058/4/20058/4/2005 10:44:55 AMAFAIL
Scheduled by a contractor via Hello! on 8/3/2005 at 4:33:54 PM. Contact: ###-####. cor. posted called 210.52(C) outlet spacing right of range, check for box fill cutin boxes island
ELE05-02829 Temporary Service8/3/20058/4/20058/4/2005 10:12:28 AMAPASS
###-#### JEFF OR CHRIS t/s u/g new ok
ELE05-02358 Final8/3/20058/4/20058/4/2005 9:48:47 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Tyler Bowen ok card signed
ELE05-02597 Final8/3/20058/4/20058/4/2005 9:08:41 AMAPASS
heath; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok card signed
ELE05-02816 Electrical Rough-In8/3/20058/4/20058/4/2005 8:33:02 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: steven sewell cor. do not cover posted called 300.4 nail plates and 11/4", 210.52(A) outlet spacing new part, old where walls are changed, acces to j tub, 250.102(C) needs #4 bond to nipple, 314.16 box fill, make sure of clearence by upstairs window service drop
ELE05-02790 Temporary Service8/3/20058/4/20058/4/2005 7:41:43 AMAPASS
JUSTIN; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
t/s o/h new ok