Inspections for the day of: Thursday, August 4, 2005.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-00638 FIRE-Final Inspection8/4/20058/4/20058/4/2005 4:41:08 PMPCANC
Work under this permit is encompassed by the new TI permit BLD04-02979.
BLD04-02979 FIRE-Final Inspection8/4/20058/4/20058/4/2005 3:31:01 PMPFAIL
Provide building street address numbers per plan review note # 1, repair exit discharge light at basement level, provide max occupant load sign in assembly area per note # 8, mount provided fire ext. in basement as discussed, repair remote annunciators at first floor level and test all HVAC detectors.
FIR05-00315 INSP-Supply line flush8/3/20058/4/20058/4/2005 1:57:50 PMPFAIL
Inspection was for an UG hydrostatic test and phase two UG cover inspection. Two 45 degree joints, the testing blank and a thrust block at the 90 are buried, preventing inspection The hydrostatic test was not ready.
FIR05-00304 INSP-Sprinkler Rough-in8/4/20058/4/20058/4/2005 11:33:54 AMPFAIL
Heads are overspaced in north open office area, attatch one retaining strap in west office, move hanger to within 2' of the end of an arm over in hallway, deficient locations are circled on the approved plans.
FIR05-00307 INSP-Final Inspection8/3/20058/4/20058/4/2005 10:01:14 AMAFAIL
Performed an additional test due to the suppression system being dismantled and re-assembled post original inspection.Hood system failed to operate correctly, one head did not function during the test.
FIR05-00307 INSP-Final Inspection8/4/20058/4/20058/4/2005 12:00:00 AMPPASS
Final test of hood suppression system operated correctly under test conditions, class K extinguisher has been provided and installed.
BLD05-00861 FIRE-Final Inspection8/4/20058/4/20058/4/2005 12:00:00 AMPPASS
Fire life safety passed inspection.