Inspections for the day of: Thursday, August 4, 2005.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00305 FIR-Aging Inspection8/4/20058/4/20058/5/2005 10:49:07 AM PASS
Sprinkler permit finaled
MIS05-00114 FIR-Final8/3/20058/4/20058/4/2005 4:21:16 PMPCANC
Per Mike with General Fire, hood and extinguishers have been taken care of. No access to business. Will re-inspect tomorrow.
FIR05-00381 INSP-Final Inspection8/3/20058/4/20058/4/2005 3:13:14 PMPCANC
This is Grant's phone. Call him 1/2 hour prior to your arrival. Thank You; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
BLD05-00450 FIRE-Final Inspection8/3/20058/4/20058/4/2005 2:53:50 PMPPART
A temporary occupancy was given with Bills permission until the fire sprinkler plans are resubmitted and approved showing the correct pendant heads used. Life safety ok to final when sprinkler permit is finaled and the shell permit is finaled which is bld###-####8
FIR05-00245 INSP-Final Inspection8/4/20058/4/20058/4/2005 2:37:14 PMPCANC
jim ; Phone #: ###-#### Canceled per Jim
BLD05-00233 FIRE-Final Inspection8/3/20058/4/20058/4/2005 2:27:18 PMPFAIL
###-#### - larry
Waited for Larry to provide plans and direction but he was busy with customers and looking up items in catalogs. No inspection performed.
BLD05-00867 FIRE-Final Inspection8/3/20058/4/20058/4/2005 12:36:44 PMAFAIL
Contact: ###-####.
Provide knox box per review note #1. Provide additional emergency light in the second floor corridor. Mount fire extinguisher on the second floor no higher than 48" to top of handle. Lower all fire extinguisher in warehouse to 48". Provide exit sign on second floor balcony as marked on sheet A2.0. Provide cfm information for all hvac units and areas served for possible duct smoke detector addition. Provide racking permits for all storage racks over 8' in height. Contact Bill Alexander for information. Provide smoke detector at the fire alarm panel. See approved drawings sheet A1.0 for locations of defiencies which include damaged fire doors and emergency lights/exit signs that need added or repaired. Several doors are also blocked by storage.
BLD04-01977 FIRE-Final Inspection8/3/20058/4/20058/4/2005 11:44:12 AMAFAIL
Provide missing canopy for the sprinkler pendant in corner, clean sprinkler pendant in the pantry, and provide annual inspection for the fire extinguishes.
BLD05-01170 FIRE-Final Inspection8/3/20058/4/20058/4/2005 9:03:39 AMAFAIL
HAROLD; Phone #: ###-#### Provide suite number and tactile exit sign per sheet A1.0
BLD04-02272 FIRE-Final Inspection8/3/20058/4/20058/4/2005 8:44:35 AMAFAIL
Duct detectors have been relocated. Of the three detectors only the one located on the south unit has the sample tube facing the correct direction and shut down properly. The other two's sample tube are incorrectly placed and the units would not go into heat mode.