Inspections for the day of: Friday, August 4, 2006.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04290 ELE-Aging Inspection8/4/20068/4/20068/7/2006 9:54:45 AM NR
talked to elect and struct, waiting for contr to call
ELE05-02260 ELE-Aging Inspection8/4/20068/4/20068/4/2006 3:14:40 PM NR
checked with contr, still needs to relocate vac motors
ELE06-02036 Final8/4/20068/4/20068/4/2006 3:12:24 PMPPASS
eric; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley looked at signs, ok to final,(front sign doesn't have power per elect)
ELE06-02668 Electrical Rough-In8/4/20068/4/20068/4/2006 3:09:12 PMPPASS
cory - underground light pole bases in parking area; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley 2 light bases u/g ok at bases only
ELE06-02880 Electrical Rough-In8/4/20068/4/20068/4/2006 2:17:53 PMPPASS
UNDERGROUND INSPECTION FOR SWIMMING POOL. THANKS; Phone #: ###-#### Internet Inspection Request from: Barry Kendall u/g for conduit only ok to cover
ELE06-02510 Electrical Rough-In8/4/20068/4/20068/4/2006 2:03:16 PMPPASS
Scheduled by a contractor via Hello! on 8/4/2006 at 11:25:11 AM. Contact: ###-####. ric ok
ELE06-02879 Rough-In Permanent Service8/4/20068/4/20068/4/2006 1:19:18 PMPCANC
brian; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles see p/s and ri
ELE06-02879 Electrical Rough-In8/4/20068/4/20068/4/2006 1:18:49 PMPFAIL
brian; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 210.52(A)(1) 2' wall in kitchen shall have recpt, BCC job address shall be posted,job id sticker shall be posted, all make-up shall be done,tub accesss shall be per mfgr's instructions, jetted tub ok for label, NOTE change permit to 20 rooms
ELE06-02879 Permanent Service8/4/20068/4/20068/4/2006 1:12:58 PMPPASS
brian; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g n ok
ELE05-03150 Electrical Rough-In8/3/20068/4/20068/4/2006 11:54:16 AMAPASS
NEED SLAB INSPECTION. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok to cover u/g cust info center area only
ELE06-02708 Final8/3/20068/4/20068/4/2006 9:07:54 AMAPASS
clayton ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called contr, gave survey nec 408.4 circuit directory shall be complete,add strap back onto service riser, ok to final
ELE05-01707 ELE-Aging Inspection8/4/20068/4/20068/4/2006 8:49:16 AM DONE
called, told to verify address and call for final
ELE06-01583 Final8/3/20068/4/20068/4/2006 8:24:07 AMAFAIL
rick; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice, 210.52(A) recept shall be within 6' front room wall, 406.8(C) recpt shall not be installed in jetted tub space, 110.3(B) kitchen gfci shall operate correctly, 410.8 closet lights shall meet clearances over shelving