ELE05-04290
| ELE-Aging Inspection | 8/4/2006 | 8/4/2006 | 8/7/2006 9:54:45 AM | | NR |
|
|
talked to elect and struct, waiting for contr to call
|
ELE05-02260
| ELE-Aging Inspection | 8/4/2006 | 8/4/2006 | 8/4/2006 3:14:40 PM | | NR |
|
|
checked with contr, still needs to relocate vac motors
|
ELE06-02036
| Final | 8/4/2006 | 8/4/2006 | 8/4/2006 3:12:24 PM | P | PASS |
|
|
eric; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley looked at signs, ok to final,(front sign doesn't have power per elect)
|
ELE06-02668
| Electrical Rough-In | 8/4/2006 | 8/4/2006 | 8/4/2006 3:09:12 PM | P | PASS |
|
|
cory - underground light pole bases in parking area; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley 2 light bases u/g ok at bases only
|
ELE06-02880
| Electrical Rough-In | 8/4/2006 | 8/4/2006 | 8/4/2006 2:17:53 PM | P | PASS |
|
|
UNDERGROUND INSPECTION FOR SWIMMING POOL. THANKS; Phone #: ###-#### Internet Inspection Request from: Barry Kendall u/g for conduit only ok to cover
|
ELE06-02510
| Electrical Rough-In | 8/4/2006 | 8/4/2006 | 8/4/2006 2:03:16 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 8/4/2006 at 11:25:11 AM. Contact: ###-####. ric ok
|
ELE06-02879
| Rough-In Permanent Service | 8/4/2006 | 8/4/2006 | 8/4/2006 1:19:18 PM | P | CANC |
|
|
brian; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles see p/s and ri
|
ELE06-02879
| Electrical Rough-In | 8/4/2006 | 8/4/2006 | 8/4/2006 1:18:49 PM | P | FAIL |
|
|
brian; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 210.52(A)(1) 2' wall in kitchen shall have recpt, BCC job address shall be posted,job id sticker shall be posted, all make-up shall be done,tub accesss shall be per mfgr's instructions, jetted tub ok for label, NOTE change permit to 20 rooms
|
ELE06-02879
| Permanent Service | 8/4/2006 | 8/4/2006 | 8/4/2006 1:12:58 PM | P | PASS |
|
|
brian; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g n ok
|
ELE05-03150
| Electrical Rough-In | 8/3/2006 | 8/4/2006 | 8/4/2006 11:54:16 AM | A | PASS |
|
|
NEED SLAB INSPECTION. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok to cover u/g cust info center area only
|
ELE06-02708
| Final | 8/3/2006 | 8/4/2006 | 8/4/2006 9:07:54 AM | A | PASS |
|
|
clayton ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called contr, gave survey nec 408.4 circuit directory shall be complete,add strap back onto service riser, ok to final
|
ELE05-01707
| ELE-Aging Inspection | 8/4/2006 | 8/4/2006 | 8/4/2006 8:49:16 AM | | DONE |
|
|
called, told to verify address and call for final
|
ELE06-01583
| Final | 8/3/2006 | 8/4/2006 | 8/4/2006 8:24:07 AM | A | FAIL |
|
|
rick; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice, 210.52(A) recept shall be within 6' front room wall, 406.8(C) recpt shall not be installed in jetted tub space, 110.3(B) kitchen gfci shall operate correctly, 410.8 closet lights shall meet clearances over shelving
|