FIR05-00037
| INSP-Final Inspection | 8/2/2006 | 8/3/2006 | | P | |
|
|
bob; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
BLD05-03341
| FIRE-Final Inspection | 8/3/2006 | 8/4/2006 | 8/4/2006 3:45:09 PM | P | PASS |
|
|
Fire life safety inspection passed.
|
BLD06-00576
| FIRE-Final Inspection | 8/4/2006 | 8/4/2006 | 8/4/2006 3:42:26 PM | P | PASS |
|
|
Life safety inspection passed.
|
FIR06-00138
| INSP-Final Inspection | 8/4/2006 | 8/4/2006 | 8/4/2006 2:21:17 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
MIS06-00075
| FIR-Final | 8/4/2006 | 8/4/2006 | 8/4/2006 1:55:09 PM | P | PART |
|
|
Items on the previous correction notice have been addressed. However the provided fire extinguishers need to be certified with a current inspection tag and the lever hardware as installed at the exterior doors needs to be fail safe (single motion under a locked condition).
|
FIR06-00321
| INSP-Sprinkler Rough-in/Hydro | 8/3/2006 | 8/4/2006 | 8/4/2006 1:08:21 PM | A | PART |
|
|
Hydrostatic test of the OH sprinkler system and UG supply line passed inspection.
|
FIR06-00533
| INSP-Sprinkler Rough-in | 8/3/2006 | 8/4/2006 | 8/4/2006 12:01:49 PM | A | PART |
|
|
OH sprinkler install is good for cover at the drop ceiling areas, one line at the kitchen is out of plumb-pendents will need to be straightened, final pending ceiling tile and escutcheons at 401's.
|
BLD05-02001
| FIRE-Final Inspection | 8/4/2006 | 8/4/2006 | 8/4/2006 11:27:18 AM | P | PASS |
|
|
Required correction has been completed, inspection passed.
|
FIR06-00451
| INSP-Sprinkler Rough-in | 8/3/2006 | 8/4/2006 | 8/4/2006 10:34:02 AM | A | PART |
|
|
OH fire sprinkler rough-in is good for cover.
|