Inspections for the day of: Monday, August 4, 2008.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00188 INSP-Sprinkler Rough-in/Hydro8/4/20088/4/20088/4/2008 4:32:23 PMPPASS
See the approved plans for locations where the sprinkler piping above the hard lids can be covered.
FIR08-00487 INSP-Conference8/4/20088/4/20088/4/2008 4:20:42 PMPDONE
I stopped by the job site at 7:30 this morning and found that the underground supply line had been buried even after I had told the general contractor not too. I told him that the piping will need to be uncovered and reburied at the correct depth. I also called Randy with Shilo and let him know that the piping can not remain at the current depth and that it will need to be corrected. I had also left a message on his cell phone late friday afternoon after speaking with Sam Rogers.
BLD08-00548 FIRE-Final Inspection8/1/20088/4/20088/4/2008 3:33:58 PMAFAIL
There were no approved plans on site. No inspection was performed.
FIR08-00471 INSP-Sprinkler Rough-in/Hydro8/1/20088/4/20088/4/2008 3:33:13 PMAPASS
The tenting has been modified and the piping can now be covered. Todd was in the process of lowering the two garage sidewall heads. I will verify them at the final.
BLD07-00306 FIRE-Final Inspection8/1/20088/4/20088/4/2008 3:32:02 PMAPASS
life safety passed
BLD07-00305 FIRE-Final Inspection8/1/20088/4/20088/4/2008 3:31:31 PMAPASS
Life safety passed
BLD08-01632 FIRE-Final Inspection8/1/20088/4/20088/4/2008 11:02:03 AMAFAIL
Provide sprinkler protection in the restroom corridor, mount the "Door to Remain Unlocked...." sticker at the main exit where is is viewable, provide single action hardware as discussed at the south secondary exit door and provide a racking permit for the storage racks in the warehouse area. These racks exceed 8'-0" in height. They are roughly 9'-3" in height with carpet acouple of feet above that. Also the shelving is solid and the carpet and foam rolls are encapsulated. Also cars are being stored in the same area.
BLD08-00549 FIRE-Final Inspection8/1/20088/4/20088/4/2008 9:39:39 AMAFAIL
The exit sign at teh north exit door has not been repaired, the fire extinguishers have not been tagged and the additional fire extinguisher at the south entrance has not been provided as per the original correction notice. All other life safety items have been corrected.
BLD08-00547 FIRE-Final Inspection8/1/20088/4/20088/4/2008 9:37:41 AMAFAIL
The racking permit still needs to be provided, the duct detector and fire alarm panel are still in a trouble condition as per the original correction notice. The other items have been corrected.
FIR08-00287 FIR-Aging Inspection8/4/20088/4/20088/4/2008 7:25:31 AM NR
work is in progress