FIR08-00188
| INSP-Sprinkler Rough-in/Hydro | 8/4/2008 | 8/4/2008 | 8/4/2008 4:32:23 PM | P | PASS |
|
|
See the approved plans for locations where the sprinkler piping above the hard lids can be covered.
|
FIR08-00487
| INSP-Conference | 8/4/2008 | 8/4/2008 | 8/4/2008 4:20:42 PM | P | DONE |
|
|
I stopped by the job site at 7:30 this morning and found that the underground supply line had been buried even after I had told the general contractor not too. I told him that the piping will need to be uncovered and reburied at the correct depth. I also called Randy with Shilo and let him know that the piping can not remain at the current depth and that it will need to be corrected. I had also left a message on his cell phone late friday afternoon after speaking with Sam Rogers.
|
BLD08-00548
| FIRE-Final Inspection | 8/1/2008 | 8/4/2008 | 8/4/2008 3:33:58 PM | A | FAIL |
|
|
There were no approved plans on site. No inspection was performed.
|
FIR08-00471
| INSP-Sprinkler Rough-in/Hydro | 8/1/2008 | 8/4/2008 | 8/4/2008 3:33:13 PM | A | PASS |
|
|
The tenting has been modified and the piping can now be covered. Todd was in the process of lowering the two garage sidewall heads. I will verify them at the final.
|
BLD07-00306
| FIRE-Final Inspection | 8/1/2008 | 8/4/2008 | 8/4/2008 3:32:02 PM | A | PASS |
|
|
life safety passed
|
BLD07-00305
| FIRE-Final Inspection | 8/1/2008 | 8/4/2008 | 8/4/2008 3:31:31 PM | A | PASS |
|
|
Life safety passed
|
BLD08-01632
| FIRE-Final Inspection | 8/1/2008 | 8/4/2008 | 8/4/2008 11:02:03 AM | A | FAIL |
|
|
Provide sprinkler protection in the restroom corridor, mount the "Door to Remain Unlocked...." sticker at the main exit where is is viewable, provide single action hardware as discussed at the south secondary exit door and provide a racking permit for the storage racks in the warehouse area. These racks exceed 8'-0" in height. They are roughly 9'-3" in height with carpet acouple of feet above that. Also the shelving is solid and the carpet and foam rolls are encapsulated. Also cars are being stored in the same area.
|
BLD08-00549
| FIRE-Final Inspection | 8/1/2008 | 8/4/2008 | 8/4/2008 9:39:39 AM | A | FAIL |
|
|
The exit sign at teh north exit door has not been repaired, the fire extinguishers have not been tagged and the additional fire extinguisher at the south entrance has not been provided as per the original correction notice. All other life safety items have been corrected.
|
BLD08-00547
| FIRE-Final Inspection | 8/1/2008 | 8/4/2008 | 8/4/2008 9:37:41 AM | A | FAIL |
|
|
The racking permit still needs to be provided, the duct detector and fire alarm panel are still in a trouble condition as per the original correction notice. The other items have been corrected.
|
FIR08-00287
| FIR-Aging Inspection | 8/4/2008 | 8/4/2008 | 8/4/2008 7:25:31 AM | | NR |
|
|
work is in progress
|