Inspections for the day of: Tuesday, August 4, 2009.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-01219 Final8/4/20098/4/20098/4/2009 4:16:46 PMPPASS
ok to final, no esc this project
ELE09-00920 ELE-Aging Inspection8/4/20098/4/20098/4/2009 4:02:16 PM DONE
no activity, waiting for bld
ELE09-00919 ELE-Aging Inspection8/4/20098/4/20098/4/2009 4:01:28 PM DONE
no activity, waiting for bld
ELE09-00950 ELE-Aging Inspection8/4/20098/4/20098/4/2009 3:59:49 PM DONE
see final, no esc this project
ELE09-00950 Final8/4/20098/4/20098/4/2009 3:59:18 PMPPASS
ok to final, no esc this project
ESC09-00101 General Inspection8/4/20098/4/20098/4/2009 3:58:17 PMPPASS
looke dok
ESC09-00393 General Inspection8/4/20098/4/20098/4/2009 3:57:13 PMPPASS
looked ok
ESC09-00403 General Inspection8/4/20098/4/20098/4/2009 3:23:07 PMPPASS
looked ok, people in middle of working
ESC08-00963 General Inspection8/4/20098/4/20098/4/2009 2:43:30 PMPPASS
looked ok
ELE09-01426 Rough-In Permanent Service8/4/20098/4/20098/4/2009 2:06:27 PMPCANC
service is ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten wrong type request, see p/s, no esc this project
ELE09-01426 Permanent Service8/4/20098/4/20098/4/2009 2:05:50 PMPPASS
service is ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten p/s u/g rec ok, no esc this project
ELE08-02933 Electrical Rough-In8/4/20098/4/20098/4/2009 1:04:24 PMPFAIL
michael Phone #: ###-#### told owner he will have to get licensed electrical contractor to do further work, needs nail plates, 1 1/4" for wire, free length conductor, flush boxes with plywood wall covering, 20a circuits with wire size for laundry and bath, receptacle spacing, make-up, told owner that his permit will have to be voided
ELE09-01076 Electrical Rough-In8/3/20098/4/20098/4/2009 12:00:55 PMAPASS
jared Phone #: ###-#### ric ok, u/g ok to cover house to garage, no esc this project
ELE09-01423 Rough-In Permanent Service8/4/20098/4/20098/4/2009 9:58:24 AMAPASS
Call for code to lock box Phone #: ###-#### Internet Inspection Request from: Brandon Blackham called contractor, ric ok, p/s o/h n ok
ELE09-01419 Electrical Rough-In8/3/20098/4/20098/4/2009 9:06:24 AMAPASS
John Phone #: ###-#### ric ok, advised builder about minimum 16"x20" access opening for tub
ELE09-01392 Rough-In Permanent Service8/3/20098/4/20098/4/2009 8:28:26 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Stephen Kren NOTE: called, left message about panel and short circuit availability since transformer only about 10' away from service, ric ok, p/s u/g n ok