Inspections for the day of: Wednesday, August 4, 2010.
Number of inspections: 24
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-01719 Electrical Rough-In8/3/20108/4/20108/5/2010 8:22:00 AMPCANC
Pool Bonding and underground. Three light niches and 4 brass sleeves, (two inside the pool and two south of the pool in decking) Phone #: ###-#### >> Inspection requested via web by Lynn Cable see response on 8-5-10
ELE10-01653 Electrical Rough-In8/3/20108/4/20108/5/2010 7:54:01 AMPCANC
west side wall cover//Kevin Phone #: ###-#### see response 8-5-10
ELE10-01564 Electrical Rough-In8/3/20108/4/20108/4/2010 3:59:06 PMPPASS
Above grid inspection
Job-site contact Kotton at ###-#### Phone #: ###-#### >> Inspection requested via web by Lynn Cable ok cover ceiling
ELE10-01650 Electrical Rough-In8/3/20108/4/20108/4/2010 3:38:58 PMPPASS
Mike-inspection for cover Phone #: ###-#### ri ok
ELE10-01703 Electrical Rough-In8/4/20108/4/20108/4/2010 3:10:39 PMPPASS
Les Chaney Phone #: ###-#### corrections made, ri walls only ok
ELE10-01578 Permanent Service8/4/20108/4/20108/4/2010 2:08:00 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Cyndi Dale corredtions made, p/s o/h rec ok
ELE10-01711 Temporary Service8/3/20108/4/20108/4/2010 1:21:06 PMAPASS
set temp power pole ready to be energized. Phone #: ###-#### >> Inspection requested via web by David Oliver t/s u/g n ok
ELE10-01705 Rough-In Permanent Service8/3/20108/4/20108/4/2010 12:27:21 PMPCANC
Phone #: ###-#### >> Inspection requested via web by Josh Craig see ri
ELE10-01705 Electrical Rough-In8/4/20108/4/20108/4/2010 12:27:00 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Josh Craig n ri ok
ELE10-01184 Final8/3/20108/4/20108/4/2010 11:53:12 AMAPASS
Please call Travis for front door lock box number at ###-####. Phone #: ###-#### >> Inspection requested via web by Lynn Proctor ok, signed card
ELE10-01652 Final8/3/20108/4/20108/4/2010 11:48:39 AMAPASS
If you have any questions, please give Clay a call. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan called, left message, ok final
GCE10-00088 GCE-Rough-In8/3/20108/4/20108/4/2010 11:47:37 AMANR
Scope: Rough-InContact: Daniel @ ###-####Call in advance needs to add outlets, 1 1/4", make-up
ELE10-01639 Electrical Rough-In8/4/20108/4/20108/4/2010 10:34:45 AMAPART
call me when you arrive and I can meet you at the guard station. Phone #: ###-#### >> Inspection requested via web by Ron Zimmerman walls only anop
ELE10-01611 Electrical Rough-In8/3/20108/4/20108/4/2010 9:31:38 AMAPART
Ceiling Perimeter Phone #: ###-#### >> Inspection requested via web by Clint Tate ceiling borders north 1/2 2nd floor only ok
ELE10-01336 Final8/3/20108/4/20108/4/2010 9:00:24 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Sean DeLacy ok signed structural card
ELE10-01578 Final8/4/20108/4/20108/4/2010 8:44:40 AMPCANC
Phone #: ###-#### >> Inspection requested via web by Cyndi Dale Inspection cancelled from web by: Cyndi Dale
ELE10-01703 Electrical Rough-In8/3/20108/4/20108/4/2010 8:21:37 AMAFAIL
les ###-#### called, left corredction notice, NEC 300.4(A)&(D) edge of bored holes and cables shall be 1 1/4" from edge of framing members, 110.12(A) shall close unused openings, 330.30(A) shall secure mc cable within 12'" of box, 358.30(A) shall secure ent within3' of box, NOTE corrections shall be made within 5 working days or further action will be taken
ELE10-01223 ELE-Aging Inspection8/4/20108/4/20108/4/2010 6:31:59 AM DONE
suc
ELE09-01497 ELE-Aging Inspection8/4/20108/4/20108/4/2010 6:30:42 AM DONE
suc
ELE09-01494 ELE-Aging Inspection8/4/20108/4/20108/4/2010 6:29:55 AM DONE
suc
ELE08-01186 ELE-Aging Inspection8/4/20108/4/20108/4/2010 6:28:28 AM DONE
see doc expire
ELE08-01186 DOC - Permit Expired8/4/20108/4/20108/4/2010 6:28:15 AMAPASS
no activity
ELE08-01244 ELE-Aging Inspection8/4/20108/4/20108/4/2010 6:26:28 AM DONE
see doc expire
ELE08-01244 DOC - Permit Expired8/4/20108/4/20108/4/2010 6:26:16 AMAPASS