ELE10-01719
| Electrical Rough-In | 8/3/2010 | 8/4/2010 | 8/5/2010 8:22:00 AM | P | CANC |
|
|
Pool Bonding and underground. Three light niches and 4 brass sleeves, (two inside the pool and two south of the pool in decking) Phone #: ###-#### >> Inspection requested via web by Lynn Cable see response on 8-5-10
|
ELE10-01653
| Electrical Rough-In | 8/3/2010 | 8/4/2010 | 8/5/2010 7:54:01 AM | P | CANC |
|
|
west side wall cover//Kevin Phone #: ###-#### see response 8-5-10
|
ELE10-01564
| Electrical Rough-In | 8/3/2010 | 8/4/2010 | 8/4/2010 3:59:06 PM | P | PASS |
|
|
Above grid inspection Job-site contact Kotton at ###-#### Phone #: ###-#### >> Inspection requested via web by Lynn Cable ok cover ceiling
|
ELE10-01650
| Electrical Rough-In | 8/3/2010 | 8/4/2010 | 8/4/2010 3:38:58 PM | P | PASS |
|
|
Mike-inspection for cover Phone #: ###-#### ri ok
|
ELE10-01703
| Electrical Rough-In | 8/4/2010 | 8/4/2010 | 8/4/2010 3:10:39 PM | P | PASS |
|
|
Les Chaney Phone #: ###-#### corrections made, ri walls only ok
|
ELE10-01578
| Permanent Service | 8/4/2010 | 8/4/2010 | 8/4/2010 2:08:00 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Cyndi Dale corredtions made, p/s o/h rec ok
|
ELE10-01711
| Temporary Service | 8/3/2010 | 8/4/2010 | 8/4/2010 1:21:06 PM | A | PASS |
|
|
set temp power pole ready to be energized. Phone #: ###-#### >> Inspection requested via web by David Oliver t/s u/g n ok
|
ELE10-01705
| Rough-In Permanent Service | 8/3/2010 | 8/4/2010 | 8/4/2010 12:27:21 PM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Josh Craig see ri
|
ELE10-01705
| Electrical Rough-In | 8/4/2010 | 8/4/2010 | 8/4/2010 12:27:00 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Josh Craig n ri ok
|
ELE10-01184
| Final | 8/3/2010 | 8/4/2010 | 8/4/2010 11:53:12 AM | A | PASS |
|
|
Please call Travis for front door lock box number at ###-####. Phone #: ###-#### >> Inspection requested via web by Lynn Proctor ok, signed card
|
ELE10-01652
| Final | 8/3/2010 | 8/4/2010 | 8/4/2010 11:48:39 AM | A | PASS |
|
|
If you have any questions, please give Clay a call. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan called, left message, ok final
|
GCE10-00088
| GCE-Rough-In | 8/3/2010 | 8/4/2010 | 8/4/2010 11:47:37 AM | A | NR |
|
|
Scope: Rough-InContact: Daniel @ ###-####Call in advance needs to add outlets, 1 1/4", make-up
|
ELE10-01639
| Electrical Rough-In | 8/4/2010 | 8/4/2010 | 8/4/2010 10:34:45 AM | A | PART |
|
|
call me when you arrive and I can meet you at the guard station. Phone #: ###-#### >> Inspection requested via web by Ron Zimmerman walls only anop
|
ELE10-01611
| Electrical Rough-In | 8/3/2010 | 8/4/2010 | 8/4/2010 9:31:38 AM | A | PART |
|
|
Ceiling Perimeter Phone #: ###-#### >> Inspection requested via web by Clint Tate ceiling borders north 1/2 2nd floor only ok
|
ELE10-01336
| Final | 8/3/2010 | 8/4/2010 | 8/4/2010 9:00:24 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Sean DeLacy ok signed structural card
|
ELE10-01578
| Final | 8/4/2010 | 8/4/2010 | 8/4/2010 8:44:40 AM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Cyndi Dale Inspection cancelled from web by: Cyndi Dale
|
ELE10-01703
| Electrical Rough-In | 8/3/2010 | 8/4/2010 | 8/4/2010 8:21:37 AM | A | FAIL |
|
|
les ###-#### called, left corredction notice, NEC 300.4(A)&(D) edge of bored holes and cables shall be 1 1/4" from edge of framing members, 110.12(A) shall close unused openings, 330.30(A) shall secure mc cable within 12'" of box, 358.30(A) shall secure ent within3' of box, NOTE corrections shall be made within 5 working days or further action will be taken
|
ELE10-01223
| ELE-Aging Inspection | 8/4/2010 | 8/4/2010 | 8/4/2010 6:31:59 AM | | DONE |
|
|
suc
|
ELE09-01497
| ELE-Aging Inspection | 8/4/2010 | 8/4/2010 | 8/4/2010 6:30:42 AM | | DONE |
|
|
suc
|
ELE09-01494
| ELE-Aging Inspection | 8/4/2010 | 8/4/2010 | 8/4/2010 6:29:55 AM | | DONE |
|
|
suc
|
ELE08-01186
| ELE-Aging Inspection | 8/4/2010 | 8/4/2010 | 8/4/2010 6:28:28 AM | | DONE |
|
|
see doc expire
|
ELE08-01186
| DOC - Permit Expired | 8/4/2010 | 8/4/2010 | 8/4/2010 6:28:15 AM | A | PASS |
|
|
no activity
|
ELE08-01244
| ELE-Aging Inspection | 8/4/2010 | 8/4/2010 | 8/4/2010 6:26:28 AM | | DONE |
|
|
see doc expire
|
ELE08-01244
| DOC - Permit Expired | 8/4/2010 | 8/4/2010 | 8/4/2010 6:26:16 AM | A | PASS |
|
|
no activity
|