Inspections for the day of: Monday, August 4, 2014.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00380 INSP-Alarm Testing8/4/20148/4/20148/4/2014 4:56:00 PMPPART
Completed satisfactory testing of the voice evac and occupant notification appliances. MP stations and SD at the panel tested okay. Items needed prior to final include tie-in and monitoring of the ansul system, test duct detectors and fire sprinkler monitoring, post signage at the door the FACP room. Provide plan modification to reflect changes in field installation from original design including zones, one-lines, location of the panel, number of initiating devices, etc.
BLD14-00472 FIRE-Final Inspection8/4/20148/4/20148/4/2014 3:30:53 PMPPASS
Life safety inspection passed. *Note- closures at the warehouse door 110 and break room door 112 to be installed prior to structural final.
FIR14-00488 INSP-Final Inspection8/1/20148/4/20148/4/2014 3:28:30 PMPPASS
Fire alarm testing completed satisfactory. Permit finaled.
BLD14-02077 FIRE-Final Inspection8/4/20148/4/20148/4/2014 3:27:35 PMPPASS
Previous C/N items completed. Life safety inspection passed.
FIR14-00252 INSP-Sprinkler Rough-in/Hydro8/1/20148/4/20148/4/2014 8:09:27 AMACANC
Please call 45 mintures prior to inspection. Leroy is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus