FIR14-00497
| INSP-Final Inspection | 8/4/2014 | 8/4/2014 | 8/4/2014 3:23:00 PM | A | CANC |
|
|
Cancel per Brian and I's discussion. Call for access Phone #: 2089411846 >> Inspection requested via mobile web by Brian A
|
BLD14-01057
| FIRE-Final Inspection | 8/1/2014 | 8/4/2014 | 8/4/2014 3:22:26 PM | A | FAIL |
|
|
Need to repair the emergency light and get a final inspection on the Alarmco fire alarm permit.
|
FIR14-00450
| INSP-Final Inspection | 8/4/2014 | 8/4/2014 | 8/4/2014 2:57:50 PM | A | PASS |
|
|
Permit finaled
|
FIR14-00228
| INSP-Sprinkler Rough-in | 8/4/2014 | 8/4/2014 | 8/4/2014 2:54:33 PM | P | PASS |
|
|
The remaining sprinkler piping is ok to cover
|
FIR13-00612
| INSP-Sprinkler Rough-in/Hydro | 8/4/2014 | 8/4/2014 | 8/4/2014 2:30:17 PM | P | FAIL |
|
|
Overhead hydro tests failed due to visable leakage at multiple pendant heads. Also two pendant heads deflectors have been damaged.
|
BLD14-00486
| FIRE-Final Inspection | 8/4/2014 | 8/4/2014 | 8/4/2014 1:57:45 PM | P | PASS |
|
|
Life safety passed. The non-functional emergency light to be repaired prior to a building sign off per agreement.
|
FIR14-00522
| INSP-Final Inspection | 8/4/2014 | 8/4/2014 | 8/4/2014 12:02:40 PM | P | CANC |
|
|
Final for IP/GSM 4G Fire Communicator Phone #: ###-#### >> Inspection requested via web by Jeremy Berg Inspection cancelled from web by: Jeremy Berg
|
FIR14-00371
| INSP-Final Inspection | 8/4/2014 | 8/4/2014 | 8/4/2014 9:57:27 AM | P | PASS |
|
|
Permit finaled
|
FIR14-00371
| INSP-Final Inspection | 8/1/2014 | 8/4/2014 | 8/4/2014 8:16:55 AM | A | FAIL |
|
|
Heat detector is mounted too close to a supply register. No testing performed.
|
FIR14-00285
| INSP-Final Inspection | 8/1/2014 | 8/4/2014 | 8/4/2014 8:09:55 AM | A | CANC |
|
|
Please call 1/2 hr prior to inspecion. Mark J is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|