BLD13-02425 FIRE-Final Inspection8/4/20158/4/20158/4/2015 4:13:57 PMPPASS
Fire life safety inspection of new apartment building, including test of exit signs and emergency lighting units throughout the building. Several EM lights need to be repaired/replaced. Also need additionl exit signs in south corridor (all floors) to clearly indicate the direction of egress to the southeast exit stair.
EVAC plans need to be installed.
Fire Exting. OK
****AS PER sja FINAL PASSED****
FIR14-00898 INSP-Final Inspection8/4/20158/4/20158/4/2015 4:07:37 PMPPART
Completion of fire alarm system testing, including test os all HVAC shutdown SDS that were not operating last visit. Tested DP valves in PG, however one system (north side) did not operate correctly. Tested all notification devices in garage that were missing at last inspection.
Fire alarm system testing completed, except for fire sprinklers that need to be completed and retested.
FIR14-00603 INSP-Sprinkler Rough-in8/3/20158/4/20158/4/2015 4:03:49 PMAFAIL
Trip test of dry pipe systems protecting the parng garage. The south system tested OK, wheras the north system did not meet 60 seconds trip test. Suspected some blockage within system. Will retest after the problem is addressed.
FIR14-00687 INSP-Sprinkler Rough-in/Hydro8/4/20158/4/20158/4/2015 4:00:57 PMPPART
RTC inspection for west dry system in parking garage. Need to add 4 DP heads in south west corner. Otherwise OK to cover the pipe for this system.
FIR15-00096 INSP-Sprinkler Rough-in8/4/20158/4/20158/4/2015 3:55:29 PMPPART
RTC inspection for 3rd floor corridors (all sides), including elevator lobbies. Need to add (1) A/S in center lobby, near east hallway. Otherwise OK to cover 3rd floor corridor pipe.
Also inspected 2nd floor elevator lobbies - center and south sides. OK to cover the pipe in these areas.
FIR14-00815 INSP-Final Inspection8/3/20158/4/20158/4/2015 12:39:20 PMAPART
Final inspection of corridors and residential units for floors 2 and 3. 4th floor not ready for insection this visit.
FIR14-00815 INSP-Sprinkler Rough-in8/3/20158/4/20158/4/2015 12:36:14 PMAPASS
This is a dry system trip for 4/1 north.
FIR14-00708 INSP-Sprinkler Rough-in8/3/20158/4/20158/4/2015 12:23:23 PMAPART
RTC inspection for hard lids in Bldg G- 1st, 2nd, 3rd floors. See plans for areas inspected today. OK to cover these areas.
FIR14-00792 INSP-Sprinkler Rough-in8/3/20158/4/20158/4/2015 12:21:23 PMAPART
RTC inspection for hard lid areas for the 2nd floor - Bldg H. See plans for areas inspected.
OK to cover piping inspected today.
FIR14-00815 INSP-Final Inspection8/3/20158/4/20158/3/2015 2:18:55 PMPCANC
Final inspections pending completion of dry pipe valve trip testing. Final walkthroughs inspections will be conducted only after all painting is completed. Some stairwells still be ing painted.