Inspections for the day of: Tuesday, August 4, 2015.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-01527 FIRE-Conference7/31/20158/4/20158/4/2015 1:54:38 PMACANC
Attempted to contact Melissa Phone #: ###-####, twice, both times no answer, phone call went to voicemail, point of contacts voicemail box was full, could not leave a message.
FIR15-00515 INSP-Sprinkler Rough-in8/4/20158/4/20158/4/2015 1:46:51 PMPPASS
Rough to cover inspection passed/complete, overhead fire sprinkler piping approved for cover
FIR15-00221 INSP-Sprinkler Rough-in8/3/20158/4/20158/4/2015 1:20:07 PMPPASS
Overhead fire sprinkler piping and tenting approved for cover
BLD15-02668 FIRE-Final Inspection8/4/20158/4/20158/4/2015 11:25:29 AMPFAIL
All exit signs inside of tenant space were not illuminated at time of inspection, exit signs are required to stay illuminated at all times. Exit discharge landings do not have emergency egress illumination, exit discharge landings are required to have emergency egress illumination. Exit signs not installed by the two east side exit discharge doors, exit sign in north/south corridor is one sided, due to location of exit sign both sides of exit sign need to indicated exit and direction of travel. More than one door associated with tenant space have double-keyed deadbolts on exterior doors, tenant space allowed one double-keyed deadbolt lock. Interior door hardware in tenant space are paddle type door handles but door handles are not single action, if locked from inside the room doors do not unlock without twisting the lock mechanism on door handle. Fire extinguishers need to be mounted, not less than 4 inches to bottom of extinguisher, not more than 48 to extinguisher mechanism.
BLD15-01817 FIRE-Final Inspection8/3/20158/4/20158/4/2015 10:16:49 AMAFAIL
Area's where egress lighting was located on the approved city drawimgs were not installed at time of inspection, was informed by the on site point of contact, Dave phone # ###-####, that the lights were damaged on delivery and that they are on order and in route. No fire alarm notification in remodeled tenenat space, checked the adjoining tenant space and corridirs, horns and strobes are in place, contractor needs to contact a fire alarm company, perform a site survey and submit for an FIR permit for alarm addition/modifications.
FIR15-00228 INSP-Sprinkler Rough-in8/3/20158/4/20158/4/2015 8:38:22 AMAPART
Rough to cover inspection passed/complete, notated area's approved for cover with red ink on city approved drawings.
FIR15-00208 INSP-Sprinkler Rough-in8/3/20158/4/20158/4/2015 8:02:36 AMAPASS
First floor rough to cover inspection passed/complete, entire first floor approved for cover.
FIR14-00807 INSP-Final Inspection8/3/20158/4/20158/3/2015 3:56:19 PMAPASS
Underground final inspection passed/complete
FIR14-00807 INSP-Supply line flush8/3/20158/4/20158/3/2015 3:55:30 PMADONE
Supply line flush passed/complete