Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-00736 ELE-Aging Inspection8/4/20168/4/20168/5/2016 6:45:42 AM CANC
ELE15-04035 Final8/2/20168/4/20168/4/2016 3:07:13 PMPPASS
PLEASE CALL ROBERT GATES AT ###-#### PRIOR TO INSPECTION Phone #: ###-#### Inspection requested via web by Scott Campbell
Final ok
ELE16-02072 Final8/4/20168/4/20168/4/2016 2:57:48 PMPFAIL
###-####- Called and re-opened permit. Wood support installed for vent pipe support installed in work space for electrical service. 110.26- Minimum of 30" wide and 36" deep shall be provided for service.
ELE16-01318 Conference8/4/20168/4/20168/4/2016 1:47:26 PMPDONE
Discussed with pool company grounding requirements for a aluminum drain cap for perimeter drain located less than 5' of waters edge. Bonding required due to location and metallic.
ELE16-00303 Final8/4/20168/4/20168/4/2016 1:42:08 PMPPART
###-#### TCO BSU floors 2 and 3
Temp final ok
ELE15-01348 Electrical Rough-In8/4/20168/4/20168/4/2016 1:12:59 PMPPASS
Ground Level Stack 2/3 Overhead ceiling insp at exterior soffit front entry RM 100,107,108 Phone #: ###-#### Inspection requested via web by Tom Betty
Ceiling as noted rough in ok cover
ELE16-02535 Electrical Rough-In8/4/20168/4/20168/4/2016 11:51:05 AMAPASS
service not ready at this time Phone #: ###-#### Inspection requested via web by mike brown
Lighting control panels have no over current devices. Areas with gaps between receptacle outlets will have permenant millwork installed. Upstairs remodel rough in ok cover
ELE16-00303 Electrical Rough-In8/4/20168/4/20168/4/2016 10:48:07 AMANR
TCO for floors 2 and 3. BSU stairway has lighting installed. Contact is Eric Gibson ###-####. Phone #: ###-#### Inspection requested via web by Toby Groves
3rd floor server room door needs to be lockable, install panel in door and locks. Complete center stair lighting and blank off all boxes. Room 368 still has connection issues, wrong whip.
ELE16-01799 Final8/3/20168/4/20168/4/2016 10:45:15 AMAPART
Phone #: ###-#### Inspection requested via web by kendall bender
Furniture whip needed for cubicals.
Signed card. Temp final ok
ELE16-01276 Electrical Rough-In8/3/20168/4/20168/4/2016 9:37:46 AMAPASS
Phone #: ###-#### Inspection requested via web by Mark M
Grid rough in ok cover
ELE16-02524 Final8/3/20168/4/20168/4/2016 9:37:07 AMAPART
Phone #: ###-#### Inspection requested via web by Mark M
8th floor still needs trimmed, 4th floor ok occupy
ELE16-02091 Electrical Rough-In8/3/20168/4/20168/4/2016 9:35:57 AMAPASS
Phone #: ###-#### Inspection requested via web by Mark M
South wall rough in ok cover
ELE16-02499 Permanent Service8/3/20168/4/20168/3/2016 7:30:48 AMACANC
Phone #: ###-#### >> Inspection requested via web by Bob Glenn Inspection cancelled from web by: Bob Glenn