Inspections for the day of: Thursday, August 4, 2016.
Number of inspections: 26
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-01732 Final8/4/20168/4/20168/4/2016 3:18:20 PMPFAIL
If you have any questions, please call Jared ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan
314.20 recessed boxes in combustable material shall have a listed extender(back west room)
406.6 faceplates missing (master bath&west back room)
406.6(d)(2) GFCI protection for non grounded outlets(west back room , can not locate the GFCI)
ELE15-02964 Electrical Rough-In8/4/20168/4/20168/4/2016 2:56:14 PMPPASS
call first, ###-#### Phone #: ###-#### Inspection requested via web by PAT MILLER
upstairs only ok cover
ELE16-02161 Permanent Service8/4/20168/4/20168/4/2016 2:36:35 PMPPASS
If you have any questions, please call Jared ###-####. Thank you!! Phone #: ###-#### Inspection requested via web by Clay Morgan
correction fixed, proper labels will be in place for final p/s o/h rec ok
ELE16-02160 Permanent Service8/4/20168/4/20168/4/2016 2:35:54 PMPPASS
If you have any questions, please call Jared ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan
correction fixed, proper labels will be installed for final p/s o/h rec ok
ELE16-02159 Permanent Service8/4/20168/4/20168/4/2016 2:35:10 PMPPASS
If you have any questions, please call Jared ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan
correction fixed, proper labels will be installed for final p/s o/h rec ok
ELE16-01823 Permanent Service8/4/20168/4/20168/4/2016 2:34:10 PMPPASS
If you have any questions, please call Jared ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan
correction fixed final ok proper labels will be in place for final p/s o/h rec ok
ELE16-02522 Final8/4/20168/4/20168/4/2016 1:54:57 PMPPASS
Phone #: ###-#### Inspection requested via web by Randy Fletcher
Final for dryer circuit and two branch circuits added in the basement ok
ELE15-02740 Electrical Rough-In8/4/20168/4/20168/4/2016 1:40:11 PMPPASS
Seth Phone #: ###-####
laundry/office/work area /server room suspended cielings only ok cover(u/f cable was still in place in front entry. Seth said he would make sure to havee it looked at) Discussed lobby area for a temp occ. No devices trimmed out and some missing lights.
ELE16-02283 Rough-In Permanent Service8/4/20168/4/20168/4/2016 12:59:37 PMPPASS
Phone #: ###-#### Inspection requested via web by Derek Newton
need to check for bushings in meter and panel on final/ Rough-in ok cover p/s o/h rec ok
ELE15-01578 Final8/4/20168/4/20168/4/2016 12:28:07 PMPPASS
final for service ok
ELE16-02496 Final8/4/20168/4/20168/4/2016 12:25:28 PMPPASS
200 amp mobile service Phone #: ###-#### Inspection requested via web by jamie berg
final for mobile home ok
ELE16-02528 Final8/4/20168/4/20168/4/2016 11:17:00 AMPCANC
Please call Dave ###-#### when you are on your way. If you have any questions, please call Jared ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan
no final needed at this time
ELE16-02528 Electrical Rough-In8/4/20168/4/20168/4/2016 11:16:30 AMPPASS
Please call Dave ###-####, when you are on your way. If you have any questions, please call Jared ###-####. Thank You.
Phone #: ###-#### Inspection requested via web by Clay Morgan
master closet only ok cover
ELE16-02479 Electrical Rough-In8/3/20168/4/20168/4/2016 10:17:56 AMAPASS
Cheryl Phone #: ###-####
out buildings ok cover
ELE16-01893 Final8/3/20168/4/20168/4/2016 10:03:39 AMAPASS
BOB ###-####
GARAGE CODE 4200 Phone #: ###-#### Inspection requested via web by Bob Glenn
final ok
ELE16-02529 Temporary Service8/3/20168/4/20168/4/2016 9:19:46 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
t/s u/g n ok
ELE16-01571 Electrical Rough-In8/3/20168/4/20168/4/2016 9:19:09 AMAPASS
Justin Hamby Phone #: ###-#### Inspection requested via web by Laurie Hoelscher
verified disconnecting means and listing
ELE16-01571 Final8/4/20168/4/20168/4/2016 9:18:50 AMPPASS
Justin Hamby Phone #: ###-#### Inspection requested via web by Laurie Hoelscher
final for AAA sign ok
ESC16-00303 Site Final8/4/20168/4/20168/4/2016 9:16:01 AMPPASS
site final ok
ESC16-00533 Site Final8/4/20168/4/20168/4/2016 9:12:11 AMPPASS
site final ok
ESC16-00205 Site Final8/4/20168/4/20168/4/2016 9:06:39 AMPPASS
site final ok
ELE16-02493 Electrical Rough-In8/3/20168/4/20168/4/2016 8:46:39 AMAPASS
walls, hard ceilings, ug Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
underground for drive thru menu boards, wall between eating area and playroom, dining area hard kids and bath hard lids ok cover
ELE16-02477 Final8/4/20168/4/20168/4/2016 8:20:04 AMPCANC
final inspection now that idaho power has been out to hook up Phone #: ###-#### >> Inspection requested via web by Randy Fletcher Inspection cancelled from web by: Randy Fletcher
ELE12-01934 ELE-Aging Inspection8/4/20168/4/20168/4/2016 7:50:02 AM CANC
too busy
ELE12-02132 ELE-Aging Inspection8/4/20168/4/20168/4/2016 7:49:46 AM CANC
too busy
ELE13-01961 ELE-Aging Inspection8/4/20168/4/20168/4/2016 7:49:34 AM CANC
too busy