FIR16-00344
| INSP-Sprinkler Rough-in/Hydro | 8/4/2016 | 8/4/2016 | 8/4/2016 3:38:30 PM | P | PART |
|
|
24 hour air test started at 3:00 pm.
|
BLD16-01581
| FIRE-Final Inspection | 8/4/2016 | 8/4/2016 | 8/4/2016 3:18:49 PM | P | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, maglock release tested with fire alarm activation, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
|
FIR16-00365
| INSP-Final Inspection | 8/4/2016 | 8/4/2016 | 8/4/2016 3:17:23 PM | P | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
FIR16-00075
| INSP-Final Inspection | 8/3/2016 | 8/4/2016 | 8/4/2016 3:16:50 PM | P | PASS |
|
|
Final fire sprinkler inspection complete for level 9.
|
BLD15-02368
| FIRE-Final Inspection | 8/3/2016 | 8/4/2016 | 8/4/2016 3:16:04 PM | A | PART |
|
|
Fire sprinkler inspections have been completed for TI section of levels 5, 6, 7, and 8. Fire alarm inspection for audio visual devices (floor above and floor below alarm notification has been tested and is satisfactory, level 4 has core and shell audio visual, no tenant improvement visuals at time of this inspection) have been completed on TI section of levels 5, 6, 7, and 8, in-duct detectors will need to be tested when the post fire smoke evacuation system is completed. Fire extinguishers are in place on levels 5, 6, 7, and 8, some of the fire extinguishers need to be inspected and tagged, fire extinguisher tags will be verified during final inspection at completion of entire project. Life fire safety inspection complete for TI levels 5, 6, 7 and 8 with exception to the fire extinguisher inspection tags and post fire smoke evacuation system.
|
FIR14-00887
| INSP-Sprinkler Rough-in | 8/4/2016 | 8/4/2016 | 8/4/2016 11:09:36 AM | P | PART |
|
|
Rough to cover inspection complete for overhead fire sprinkler piping located on level 3, level 3 overhead fire sprinkler piping approved for cover.
|
FIR16-00338
| INSP-Final Inspection | 8/3/2016 | 8/4/2016 | 8/4/2016 10:23:44 AM | A | PASS |
|
|
Final commercial hood fire suppression system inspection passed/complete.
|
BLD16-00920
| FIRE-Final Inspection | 8/3/2016 | 8/4/2016 | 8/4/2016 9:52:02 AM | A | PASS |
|
|
Fire sprinkler inspection complete, no fire alarm modifications, fire extinguisher is in common area with current inspection tag. Noted that the office doors on mezzanine have thumbturn deadbolts installed on doors for security, door handles are paddle type door hardware. Final life fire safety inspection passed/complete.
|
BLD15-01619
| FIRE-Final Inspection | 8/3/2016 | 8/4/2016 | 8/4/2016 9:48:54 AM | A | PASS |
|
|
Fire sprinkler inspection complete, no fire alarm modifications, fire extinguisher is in place with current inspection tag. Final life fire safety inspection passed/complete.
|
FIR16-00428
| INSP-Final Inspection | 8/4/2016 | 8/4/2016 | 8/4/2016 9:31:40 AM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
FIR15-00329
| INSP-Final Inspection | 8/4/2016 | 8/4/2016 | 8/4/2016 5:21:20 AM | A | PASS |
|
|
Final underground inspection passed/complete
|
FIR15-00329
| INSP-Supply line flush | 8/3/2016 | 8/4/2016 | 8/4/2016 5:19:46 AM | A | DONE |
|
|
North main line flush completed after PIV relocation.
|