BLD16-03416
| FIRE-Final Inspection | 8/4/2017 | 8/4/2017 | 8/4/2017 3:04:32 PM | P | CANC |
|
|
No life safety inspection requierd. I left message on contacts voice mail.
Joey Phone #: ###-####
|
FIR17-00401
| INSP-Final Inspection | 8/4/2017 | 8/4/2017 | 8/4/2017 2:43:26 PM | P | CANC |
|
|
Mike Phone #: ###-####
|
FIR17-00166
| INSP-Final Inspection | 8/4/2017 | 8/4/2017 | 8/4/2017 2:43:18 PM | P | CANC |
|
|
Mike Phone #: ###-####
|
BLD17-01710
| FIRE-Final Inspection | 8/3/2017 | 8/4/2017 | 8/4/2017 2:07:10 PM | A | CANC |
|
|
Please contact Kevin Staats for Access 30min Prior ###-#### Phone #: ###-#### Inspection requested via web by Brian McCoy
|
FIR17-00365
| INSP-Sprinkler Rough-in | 8/4/2017 | 8/4/2017 | 8/4/2017 2:01:23 PM | A | PART |
|
|
The underground supply piping is now installed deap enough and can be covered. The remote FDC piping has not been installed yet in the same trench. I will need another inspection scheduled prior to a complete cover inspection given.
|
BLD17-02648
| FIRE-Final Inspection | 8/4/2017 | 8/4/2017 | 8/4/2017 1:59:38 PM | P | FAIL |
|
|
Provide city approved plans, remove the thumbturn dead bolt as discussed.
|
BLD17-02526
| FIRE-Final Inspection | 8/4/2017 | 8/4/2017 | 8/4/2017 1:59:02 PM | P | FAIL |
|
|
Provide city approved plans, remove the thumb turn dead bolt from the main exit as discussed, provide a tagged fire extinguisher as discussed.
|
BLD17-02684
| FIRE-Final Inspection | 8/3/2017 | 8/4/2017 | 8/4/2017 1:15:26 PM | A | PASS |
|
|
Life safety passed
|
BLD17-00961
| FIRE-Final Inspection | 8/4/2017 | 8/4/2017 | 8/4/2017 12:24:46 PM | P | FAIL |
|
|
One of the two smoke detectors is located too close to an air register (3'-0" min.). A permit is required for this work.
|
FIR17-00356
| INSP-Sprinkler Rough-in | 8/3/2017 | 8/4/2017 | 8/4/2017 12:23:43 PM | A | PASS |
|
|
See the city approved plans for locations marked "ok" where piping is ok to cover. Also work located at the Moon's Restraunt has not been completed. If it is to be completed under another permit this permit will need to be modified to remove this work from the scope of work.
|
FIR17-00254
| INSP-Final Inspection | 8/2/2017 | 8/4/2017 | 8/4/2017 10:43:24 AM | A | PASS |
|
|
Permit finaled
|
NAF17-00053
| INSP-Final | 8/3/2017 | 8/4/2017 | 8/4/2017 10:42:51 AM | A | FAIL |
|
|
Repair the three exit signs.
|
NAF17-00023
| INSP-Sprinkler Rough-in/Hydro | 8/3/2017 | 8/4/2017 | 8/4/2017 9:57:46 AM | A | PART |
|
|
Inspection turned into a conference. Hydro test has already been performed. Earth quake bracing is not installed in the approved locations. It will need to be installed as approved or calculations resubmitted for the new locations. Retaining straps are still not installed correctly. Need cap on FDC. Need sticker on bell. Need service tag on riser. Need data sheet on the test valve that it has the correct orfice for the inspector test. Need forward flush done. And ultimately need the fire alarm interconnections verified.
|
FIR17-00392
| INSP-Final Inspection | 8/3/2017 | 8/4/2017 | 8/4/2017 9:47:51 AM | P | CANC |
|
|
Inspecting Technician: Ray McQueen Building access: building is open Building contact: Scott, ###-#### Phone #: ###-#### >> Inspection requested via web by Rose Peterson Inspection cancelled from web by: Rose Peterson
|
FIR16-00580
| INSP-Final Inspection | 8/3/2017 | 8/4/2017 | 8/4/2017 7:41:43 AM | A | PASS |
|
|
permit finaled
|
NAF17-00027
| INSP-Final | 8/3/2017 | 8/4/2017 | 8/4/2017 12:00:00 AM | A | PASS |
|
|
OK to final.
|