MEC20-03194
| Final | 7/30/2020 | 8/4/2020 | 8/4/2020 3:35:12 PM | P | PASS |
|
|
INSTALLER DAVID ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace coil in basement a/c co locking caps ok- virtual video inspection with Dave onsite
|
MEC20-03288
| Final | 8/4/2020 | 8/4/2020 | 8/4/2020 3:06:17 PM | P | PASS |
|
|
We have the pictures of the inside and outside Inspection requested via web by Margie Rowe- electric furnace coil heat pump locking caps ok- pics sent via text of furnace coil and primary/secondary drains with wet switch
|
MEC20-03268
| Final | 8/3/2020 | 8/4/2020 | 8/4/2020 2:43:26 PM | P | NR |
|
|
Please call Craig on your way for a video inspection. - ###-####5 Phone #: ###-#### Inspection requested via web by Arielle Hendricks- still installing- reschedule when complete
|
MEC20-03272
| Final | 8/3/2020 | 8/4/2020 | 8/4/2020 2:06:33 PM | P | PASS |
|
|
Please contact our Install John prior to arriving to ensure he is ready. Thank you! Phone #: ###-#### Inspection requested via web by Rick Borg- a/c coil co locking caps ok- video of coil in basement with pics seen onsite with installer
|
MEC20-02152
| Final | 7/29/2020 | 8/4/2020 | 8/4/2020 1:30:40 PM | P | CANC |
|
|
TYLER ###-#### - CALL FOR ACCESS Phone #: ###-#### Inspection requested via web by Mike Almanza- due to COVID 19 city of Boise has suspended all inspections inside occupied homes until further notice and no date set yet- virtual video will be acceptable meeting with me onsite- talked to Mike and let him know- will schedule accordingly
|
MEC20-03242
| Final | 8/3/2020 | 8/4/2020 | 8/4/2020 1:19:49 PM | P | FAIL |
|
|
field super: Chad robertston Phone #: ###-#### Inspection requested via web by Lisa Whitney- breaker wrong size in panel- chad will check on this- send pic for reinspect
|
MEC20-03287
| DOC - Permit Finaled | 8/4/2020 | 8/4/2020 | 8/4/2020 12:52:10 PM | P | PASS |
|
|
call before 45min. before going Phone #: ###-#### Inspection requested via web by Rene Neumeyer- log set ok- damper clamp installed- co installed- virtual video onsite with installer
|
MEC20-03287
| Rough-in | 8/4/2020 | 8/4/2020 | 8/4/2020 12:51:22 PM | P | CANC |
|
|
call before 45min. before going Phone #: ###-#### Inspection requested via web by Rene Neumeyer- should have been pressure test and final- virtual video onsite with installed
|
MEC20-03287
| Pressure Test | 8/4/2020 | 8/4/2020 | 8/4/2020 12:49:54 PM | P | PASS |
|
|
call before 45min. before going Phone #: ###-#### Inspection requested via web by Rene Neumeyer- 20lb gas pass csst sleeved thru concrete
|
MEC20-03111
| Final | 8/3/2020 | 8/4/2020 | 8/4/2020 11:02:21 AM | A | CANC |
|
|
Liberty Lake Apartments, the club house. Project coordinator is Justin ###-####. Their office number is ###-####. A1 Heating is ###-####. Phone #: ###-#### Inspection requested via web by Arielle Hendricks- should have been R/I inspection see notes
|
MEC20-03111
| Rough-in | 8/4/2020 | 8/4/2020 | 8/4/2020 11:01:09 AM | A | PASS |
|
|
Liberty Lake Apartments, the club house. Project coordinator is Justin ###-####. Their office number is ###-####. A1 Heating is ###-####. Phone #: ###-#### Inspection requested via web by Arielle Hendricks- R/I on 2 bath fans 1 supply at entry and return in server room ok to cover- need to attach this permit to bld by final- server room will need framing completed and roll up door remove at final
|
MEC20-02846
| Rough-in | 8/4/2020 | 8/4/2020 | 8/4/2020 10:40:05 AM | A | PASS |
|
|
R/I ok
|
MEC20-03264
| Final | 8/3/2020 | 8/4/2020 | 8/4/2020 10:24:03 AM | A | NH |
|
|
Please call Chris prior to inspection to be sure he is there. His wife is due to have baby tomorrow. ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- called Chris they were at a doctor appoinment- will reschedule per conversation on phone
|
MEC17-05182
| Conference | 8/3/2020 | 8/4/2020 | 8/4/2020 10:08:35 AM | A | CANC |
|
|
screened -call 15 minutes ahead - new addition // Vladimir Phone #: ###-####- final completed
|
MEC17-05182
| DOC - Permit Finaled | 8/4/2020 | 8/4/2020 | 8/4/2020 10:08:20 AM | A | PASS |
|
|
screened -call 15 minutes ahead - new addition // Vladimir Phone #: ###-####- final ok
|
MEC20-03263
| Final | 8/3/2020 | 8/4/2020 | 8/4/2020 9:45:59 AM | A | FAIL |
|
|
Furnace in garage. Homeowner works from home. Tony Edgett ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace a/c coil co locking caps ok- primary drain off coil open tee shall de higher than secondary switch- need to add 3 inches to get above- send pic for reinspect
|
MEC20-03258
| Rough-in | 8/3/2020 | 8/4/2020 | 8/4/2020 9:33:37 AM | A | NR |
|
|
screened - garage addition // Camron Phone #: ###-####- need pvc drains off 3 units installed to outside- need energy star rated fan for continuos or intermittent for mini split heads with timer- recall in when fan and pvc drains done- went over onsite with there dad
|
MEC20-01343
| Mec-Request for Extension | 8/3/2020 | 8/4/2020 | 8/4/2020 8:56:51 AM | A | PASS |
|
|
We are close to finishing the project, can you do a parcel inspection so we dont loose the building permit, it''s going to expire soon. Phone #: ###-#### Inspection requested via web by Oleg Chervak- permit extended til 11-4-20-
|
MEC20-03239
| Final | 7/31/2020 | 8/4/2020 | 8/4/2020 8:55:34 AM | A | PASS |
|
|
Please call Dennis at ###-#### before heading to jobsite, thanks! Phone #: ###-#### Inspection requested via web by Dennis Fox- furnace a/c coil co locking caps ok
|
MEC20-02407
| Final | 8/4/2020 | 8/4/2020 | 8/4/2020 8:42:57 AM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Randy Hart Inspection cancelled from web by: Randy Hart
|
MEC20-02458
| Final | 8/3/2020 | 8/4/2020 | 8/4/2020 8:37:35 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Matthew BLANKENSHIP- need timer installed on energy star fan in laundry room for mechanical ventilation
|
MEC20-02405
| Final | 7/30/2020 | 8/4/2020 | 8/4/2020 8:27:55 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart 1- need locking caps on a/c service ports 2- need lower combustion installed 3- need duct blast test completed
|
MEC20-02406
| Final | 7/30/2020 | 8/4/2020 | 8/4/2020 8:27:04 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart 1- need duct blast test completed 2- need approved man j onsite 3- need locking caps on a/c service ports
|
MEC20-02407
| Final | 8/3/2020 | 8/4/2020 | 8/4/2020 8:26:09 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart 1- need approved man i onsite 2- need duct blast completed
|
MEC20-02404
| Final | 8/3/2020 | 8/4/2020 | 8/4/2020 8:25:30 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart
|
MEC20-02372
| Final | 7/31/2020 | 8/4/2020 | 8/4/2020 7:54:35 AM | A | CANC |
|
|
This is a Flue Pressure and Final Inspect. Please meet our installer at home at 9:00 AM. Contact for Right Now is Mary ###-#### Phone #: ###-#### >> Inspection requested via web by Mary LaFayette Inspection cancelled from web by: Mary LaFayette
|
MEC19-04499
| Mec-Aging Inspection | 8/4/2020 | 8/4/2020 | 8/4/2020 7:53:09 AM | | CANC |
|
|
permit expired
|
MEC19-04499
| DOC - Permit Expired | 8/4/2020 | 8/4/2020 | 8/4/2020 7:52:55 AM | A | PASS |
|
|
permit expired- no calls no activity
|
MEC19-04489
| Mec-Aging Inspection | 8/4/2020 | 8/4/2020 | 8/4/2020 7:51:56 AM | | CANC |
|
|
permit expired
|
MEC19-04489
| DOC - Permit Expired | 8/4/2020 | 8/4/2020 | 8/4/2020 7:51:44 AM | A | PASS |
|
|
permit expired- no calls no activity
|