Inspections for the day of: Monday, August 5, 1996.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE96-02537 INSP - Permanent service8/5/19968/5/19968/5/1996 12:00:00 AM PASS
/ / 315 - 53 ok jf 200a u/g new
ELE96-02551 INSP - Electrical Rough-In8/5/19968/5/19968/5/1996 12:00:00 AM PASS
08/05/96 315 - CIRCUIT EXTENSION- GATED ENTRY- KEN WILEY OWNER 09 ok jf
ELE95-01320 INSP - Permanent service8/2/19968/5/19968/5/1996 12:00:00 AMAPASS
08/05/96 315 - BASEMENT OF ST. AL'S ORTHO CLINIC- 1ST FLOOR OF SW WING 5
ELE96-02110 INSP - Final8/1/19968/5/19968/5/1996 12:00:00 AMAPASS
08/05/96 315 - CALL HARLEY MILLER ###-#### FOR ACCESS- HOT TUB 14 ok jf cor.notice PLass posted, corrections made
ELE96-02537 INSP - Ele Rough-In/Perm Svc8/2/19968/5/19968/5/1996 12:00:00 AMAFAIL
08/05/96 315 - part. jf had to leave job to check on code question with 09 failed cor. and do not cover posted NEC,250-114(b),110-14(a) terminat wires properly at ceiling boxes,300-21 needs ceiling rated boxes in gara
ELE96-02542 INSP - Permanent service8/5/19968/5/19968/5/1996 12:00:00 AMPFAIL
08/05/96 315 - 53 failed jf cor. posted BCC,4-5-54 no violations to be r bond service properly, 250-80&81(a) grd or bond to metal water piping,200-6(a)&(b) ID neutrals properly, 110-14 use cool aid on alum. w
ELE96-02544 INSP - T/S and Final8/5/19968/5/19968/5/1996 12:00:00 AMPPASS
08/05/96 315 - 49&14 ok jf u/g new
ELE96-02547 INSP - Permanent service8/5/19968/5/19968/5/1996 12:00:00 AMPCANC
08/05/96 315 - permit to be voided not in the city jf
ELE96-02550 INSP - Ele Rough-In/Perm Svc8/5/19968/5/19968/5/1996 12:00:00 AMPPASS
08/05/96 315 - 09&53 ok jf 14rms 1a/c 200a u/g new