Inspections for the day of: Tuesday, August 5, 1997.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMarv Burrus
TitleELE
Phone #340-1297
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE96-04136 INSP - Electrical Rough-In8/5/19978/5/19978/6/1997 12:00:00 AMPPART
08/05/97 403 - cover inspection on the 5th floor bathroom
ELE97-00863 INSP - Electrical Rough-In8/5/19978/5/19978/6/1997 12:00:00 AMPPART
08/05/97 403 - hallways and new panel board
ELE97-02052 INSP - Final8/5/19978/5/19978/6/1997 12:00:00 AMPPASS
08/05/97 403 - either be open or the key will be under the mat
ELE97-02087 INSP - Permanent service8/4/19978/5/19978/5/1997 12:00:00 AMAPASS
08/04/97 403 - ###-#### Skip if there is a problem then call him and he
ELE97-00430 INSP - Electrical Rough-In8/4/19978/5/19978/5/1997 12:00:00 AMAPASS
08/04/97 403 - rough-in on the walls. 3RD FLOOR FLOOR INTERMEDIATE LEVEL LID CEILING IN ROOMS EXCEPT ROOMS # 221, 215, 206, 207, 225, 226, 227, &
ELE97-02581 INSP - Air conditioning8/4/19978/5/19978/5/1997 12:00:00 AMANH
08/04/97 403 - LEFT CARD...
ELE97-01980 INSP - Final8/4/19978/5/19978/5/1997 12:00:00 AMAPASS
08/04/97 403 -
ELE97-02584 INSP - Conference8/5/19978/5/19978/5/1997 12:00:00 AMPPASS
08/05/97 403 - DISCUSSED CODE REQUIREMENTS FOR CODE REQUIREMENTS.
ELE97-02595 INSP - Permanent service8/5/19978/5/19978/5/1997 12:00:00 AMPPASS
08/05/97 403 - ASAP
ELE97-01063 INSP - Final8/5/19978/5/19978/5/1997 12:00:00 AMPPASS
08/05/97 403 - one recess can trim on order. above bathtub in master, wi it gets here. per dan mtn. valley elec. WAS INSTALLED...MB
ELE97-02574 INSP - Ele Rough-In/Perm Svc8/5/19978/5/19978/5/1997 12:00:00 AMPFAIL
08/05/97 403 - NEC: 230-6. SERVICE ENTERANCE CONDUCTORS IN PVC RACEWAY INSIDE GARAGE. NEC: 333-12. BE REQUIRED WITHIN 6FT. OF ATTIC ACCESS. BOISE ENERGY CODE 1205-C. TIMER AND MANUAL SWITCH REQUIRED FOR IN HOUSE
ELE97-02575 INSP - Ele Rough-In/Perm Svc8/5/19978/5/19978/5/1997 12:00:00 AMPFAIL
08/05/97 403 -NEC: 230-6. PVC CONDUIT FROM METER FOR SERVICE ENTRANCE CONDUCTORS INSIDE GARAGE SHALL NOT BE PERMITTED. NEC: 333-12. PROTECTION SHALL BE REQUIRED FOR CABLES WITHIN 6FT OF ATTIC ACCESS. BOISE CITY ENERGY CODE:1205-C. TIMER AND MANUAL SWITCH REQUIRED FOR IN HOUSE FAN.
ELE97-02576 INSP - Ele Rough-In/Perm Svc8/5/19978/5/19978/5/1997 12:00:00 AMPFAIL
08/05/97 403 - NEC:230-6. SERVICE ENTRANCE CONDUCTORS IN PVC CONDUIT IN GARAGE FROM METER SHALL NOT BE ALLOWED. NEC: 333-12. PROTECTION FOR CABLES SHALL BEREQUIRED FOR WITHIN 6FT. OF ATTIC ACCESS.
ELE97-02578 INSP - Ele Rough-In/Perm Svc8/5/19978/5/19978/5/1997 12:00:00 AMPFAIL
08/05/97 403 - NEC:230-6. PVC CONDUIT FROM METER INSIDE GARAGE FOR SERVICE ENTRANCE CONDUCTORS SHALL NOT BE ALLOWED. NEC: 333-12. CABLES WITHIN 6FT OF ATTIC ACCESS SHALL BE PROTECTED. BOISE CITY ENERGY CODE 1205-C. TIMER AND MANUAL SWITCH FOR IN HOUSE FAN REQUIRED.