FIR02-00294
| INSP-Supply line flush | 8/2/2002 | 8/5/2002 | 8/5/2002 12:00:00 AM | A | FAIL |
|
|
the thrust block pored by the contractor at the united water tie-in completly covers all of the pipe and fittings. There is no way to verify pipe, fittings or installation. I left correction notice asking contractor to remove thrust block so items can be verified 8/5/2002 9:13:40 AM
|
FIR02-00294
| INSP-Sprinkler Rough-in/Hydro | 8/5/2002 | 8/5/2002 | 8/5/2002 12:00:00 AM | A | PASS |
|
|
Underground tie-in to the united water line OK for cover
|
BLD02-00064
| FIRE-Final Inspection | 8/5/2002 | 8/5/2002 | 8/5/2002 12:00:00 AM | P | FAIL |
|
|
duct detector needs to be tested and door hardware installed 8/5/2002 3:37:10 PM
|
FIR02-00276
| INSP-Final Inspection | 8/5/2002 | 8/5/2002 | 8/5/2002 12:00:00 AM | P | PASS |
|
|
fire sprinkler system finaled
|
FIR02-00294
| INSP-Sprinkler Rough-in/Hydro | 8/5/2002 | 8/5/2002 | 8/5/2002 12:00:00 AM | P | PASS |
|
|
bedding OK for underground supply. Underground OK for cover
|
BLD02-00933
| FIRE-Final Inspection | 8/2/2002 | 8/5/2002 | 8/5/2002 12:00:00 AM | P | PASS |
|
|
fire life/safety finaled 8/5/2002 1:14:42 PM
|