Inspections for the day of: Friday, August 5, 2005.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-02347 BLD-Aging Inspection8/5/20058/5/20058/8/2005 3:19:21 PM DONE
Pending completion and inspection of fire alarm work under permit FIR05-00048 with NW sales company per upgrade agreement.
BLD04-02979 FIRE-Final Inspection8/5/20058/5/20058/5/2005 4:58:12 PMPPASS
Fire life safety finaled.
FIR05-00155 INSP-Sprinkler Rough-in/Hydro8/2/20058/5/20058/5/2005 4:54:55 PMPPART
Attatch retaining straps to beam in nursery area 127, provide approved hanger for 11/4 pipe in hallway 108, adjust DSW at closet 163, inspect lines not yet installed at west end of sanctuary, verify final head locations after drops are cut in, all remaining areas are okay to cover.
FIR05-00460 INSP-Supply line flush8/4/20058/5/20058/5/2005 1:47:36 PMPPART
Underground fire supply line is good for cover.
BLD05-01273 FIRE-Final Inspection8/4/20058/5/20058/5/2005 11:51:04 AMAFAIL
Provide suite address for tenant as indicated on plan review notes, provide and install one 2A10BC fire ext. as discussed, verify door hardware when installed at various locations including office 109, relocate exit sign above office door 109, provide emergency light at reception room 100, paint curb directly in front of fire hydrant as discussed.
FIR05-00353 INSP-Final Inspection8/4/20058/5/20058/5/2005 11:24:19 AMAPASS
Fire alarm passed inspection.
BLD05-01671 FIRE-Conference8/4/20058/5/20058/5/2005 10:04:28 AMAPASS
Fire life safety passed inspection.
FIR05-00431 INSP-Sprinkler Rough-in8/4/20058/5/20058/5/2005 9:40:55 AMAPART
Sprinkler rough-in is okay to cover, will final permit when all ceiling tile and escutcheons are installed.
FIR05-00304 INSP-Sprinkler Rough-in8/5/20058/5/20058/5/2005 12:00:00 AMAPART
Overhead rough-in is good for cover, will final permit when all ceiling tile and escutcheons are installed.
FIR05-00315 INSP-Sprinkler Rough-in8/5/20058/5/20058/5/2005 12:00:00 AMPPART
Underground fire supply is acceptable to cover.
BLD04-00601 FIRE-Final Inspection8/5/20058/5/20058/5/2005 12:00:00 AMPPASS
Shell permit life safety passed inspection.