Inspections for the day of: Friday, August 5, 2005.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00305 INSP-Final Inspection8/5/20058/5/20058/5/2005 4:16:59 PMPPASS
Sprinkler permit finaled
FIR05-00113 INSP-Supply line flush8/5/20058/5/20058/5/2005 2:48:41 PMPPASS
Underground supply line flush passed
FIR05-00113 INSP-Sprinkler Rough-in/Hydro8/5/20058/5/20058/5/2005 2:48:02 PMPPASS
Underground hydro test passed.
FIR05-00434 INSP-Sprinkler Rough-in8/5/20058/5/20058/5/2005 2:21:15 PMPPASS
Sprinkler rough-in is ok except for aux. drains have not been installed yet and will need looked at. Also hanger rods will need to be shortened or eq bracing added on the 3" main that has been raised and the 2"x1 1/2" hex bushing used in the south below mezzanine piping cannot be used per nfpa 13. Sprinkler piping can be covered. Access door at the north stairs will be needed as stated on approved drawings.
FIR04-00349 FIR-Aging Inspection8/5/20058/5/20058/5/2005 1:36:52 PM NR
Jeff with Treasure Valley is following up on status
MIS05-00114 FIR-Conference8/4/20058/5/20058/5/2005 12:34:39 PMADONE
Kitchen hood suppression system and fire extinguishers have been inspected and tagged by General Fire. K class extinguisher tagged and provided in kitchen.
BLD03-01484 FIRE-Final Inspection8/4/20058/5/20058/5/2005 10:33:29 AMAFAIL
rick; Phone #: ###-#### No approved plans or notes on site. I talked to Rick about fire extinguisher requirements.
BLD05-00233 FIRE-Final Inspection8/4/20058/5/20058/5/2005 9:27:19 AMAPASS
Fire life safety finaled
BLD05-01398 FIRE-Final Inspection8/4/20058/5/20058/5/2005 8:43:42 AMAPASS
fire life safety finaled
FIR05-00381 INSP-Final Inspection8/4/20058/5/20058/5/2005 8:41:53 AMAPASS
Fire alarm finaled
FIR05-00433 INSP-Final Inspection8/5/20058/5/20058/5/2005 8:40:42 AMPPASS
Fire sprinklers finaled
BLD05-00368 FIRE-Final Inspection8/4/20058/5/20058/4/2005 2:52:52 PMAPART
A temporary occupancy was given with Bills permission until the fire sprinkler plans are resubmitted and approved showing the correct pendant heads used. Life safety ok to final when sprinkler permit is finaled
FIR05-00197 INSP-Final Inspection8/4/20058/5/20058/4/2005 2:52:14 PMAPART
A temporary occupancy was given with Bills permission until the fire sprinkler plans are resubmitted and approved showing the correct pendant heads used.