Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-01278 Final8/5/20088/5/20088/5/2008 4:16:44 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Lynn Cable corrections made ok to final
ESC08-00415 General Inspection8/5/20088/5/20088/5/2008 3:34:32 PMPPART
looked ok
ESC08-00113 General Inspection8/5/20088/5/20088/5/2008 3:33:40 PMPPART
looked ok
ESC08-00346 General Inspection8/5/20088/5/20088/5/2008 3:32:51 PMAPART
looked ok
ESC08-00252 General Inspection8/5/20088/5/20088/5/2008 3:31:41 PMAPART
looked ok
ESC07-01052 General Inspection8/5/20088/5/20088/5/2008 3:30:33 PMAPART
looked ok
ELE08-01567 Final8/5/20088/5/20088/5/2008 3:28:51 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Lynn Cable corrections made, ok to final
ELE08-02173 Conference8/5/20088/5/20088/5/2008 3:06:48 PMPDONE
Early as possible//Chet ###-#### talked with owner about grounding, new mast, when to call for p/s, replacement of panel to 200 amp, new service conductors, no esc this project
ELE08-01508 Electrical Rough-In8/5/20088/5/20088/5/2008 2:30:58 PMPPASS
Hello the final ceilings 2nd floor are ready for grid cover. Matt is on site Thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig ok to cover last 4 rooms 2nd floor ceilings, couldn't find plans to mark, no esc this project
ELE08-02175 Final8/5/20088/5/20088/5/2008 1:42:32 PMPNR
Phone #: ###-#### Internet Inspection Request from: Debby Ellis called contractor, told to fix door, get abrasion protection for gec and provide gfci breakers and cords, make ready for hook-up, no esc this project
ELE08-01871 Final8/5/20088/5/20088/5/2008 12:44:38 PMPPASS
danny Phone #: ###-#### ok to final, no esc this project
ELE08-02163 Electrical Rough-In8/4/20088/5/20088/5/2008 10:37:24 AMAPASS
Danny Phone #: ###-#### ric ok
ELE08-02157 Temporary Service8/4/20088/5/20088/5/2008 10:26:22 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Lynn Solmon called left correction notice, NEC 312.5 GEC abrasion protection shall use equipment listed for use, 408.4 shall provide circuit directory, 406.8(A) shall provide in-use type cover for receptacle, 406.8(B) receptacles shall be listed weather-resistant, 110.3(B) shall vvinstall listed equipment per instructions, 590.6(B) shall provide gfci protection for personnel, no esc this project
ELE08-01572 Electrical Rough-In8/4/20088/5/20088/5/2008 9:39:22 AMAPASS
Underground inspection. Phone #: ###-#### Internet Inspection Request from: Kathy Smith ok to cover under slab conduit only
ELE07-03457 Electrical Rough-In8/4/20088/5/20088/5/2008 9:01:28 AMAPASS
joe - cover Phone #: ###-#### south side aisle F u/g ok to cover
ELE08-01967 Electrical Rough-In8/4/20088/5/20088/5/2008 8:18:45 AMAPEND
This is a ceiling inspection. The contact Electrician is Jim Stansell his number is ###-####. Thank you! Phone #: ###-#### Internet Inspection Request from: Shawna Gates ok to cover ceilings, no esc this project
ELE08-01615 Electrical Rough-In8/4/20088/5/20088/4/2008 5:16:35 PMACANC
Rough-in for Snake River Pool & Spa Phone #: ###-#### Internet Inspection Request from: Jenni Keller Inspection cancelled from web by: Jenni Keller
ELE08-01616 Final8/4/20088/5/20088/4/2008 5:15:15 PMACANC
Final Electrical Inspection for childrens store Phone #: ###-#### Internet Inspection Request from: Jenni Keller Inspection cancelled from web by: Jenni Keller