FIR09-00455
| INSP-Final Inspection | 8/5/2009 | 8/5/2009 | 8/5/2009 4:04:04 PM | P | FAIL |
|
|
The griddle/stove is not 6" behind the edge of the hood as required in the IMC. The light in the hood did not shut off on suppression system activation as per Boise City Ordinance. The manual activation station is mounted too high as per the IFC. The activation of the hood suppression system did not set off the existing fire alarm system as required per the IFC and NFPA 72. The remote annunciator and the monitoring station only showed a fire trouble signal.
|
FIR08-00832
| INSP-Final Inspection | 8/5/2009 | 8/5/2009 | 8/5/2009 3:52:02 PM | P | FAIL |
|
|
Todays inspection was for completed work in this building. Everything is complete on the second floor except for the corridor.
|
FIR08-00831
| INSP-Final Inspection | 8/5/2009 | 8/5/2009 | 8/5/2009 3:50:32 PM | P | FAIL |
|
|
Todays inspection was for completed work in this building. The first and second floor is complete except for the corridors.
|
FIR08-00830
| INSP-Final Inspection | 8/5/2009 | 8/5/2009 | 8/5/2009 3:47:39 PM | A | FAIL |
|
|
Todays inspection was for completed sprinkler work for the second and third floor areas of this building. The only areas not complete are the third floor Atrium and the second floor corridor.
|
BLD09-00744
| FIRE-Final Inspection | 8/5/2009 | 8/5/2009 | 8/5/2009 2:05:05 PM | P | PASS |
|
|
life safety passed
|
BLD09-00754
| FIRE-Final Inspection | 8/5/2009 | 8/5/2009 | 8/5/2009 1:14:54 PM | P | PASS |
|
|
life safety passed
|
BLD08-02057
| FIRE-Final Inspection | 8/4/2009 | 8/5/2009 | 8/5/2009 9:54:30 AM | A | PASS |
|
|
Life safety passed.
|
FIR08-00831
| INSP-Sprinkler Rough-in | 8/4/2009 | 8/5/2009 | 8/4/2009 4:46:59 PM | A | CANC |
|
|
Duplicate inspection.
|