Inspections for the day of: Wednesday, August 5, 2009.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00455 INSP-Final Inspection8/5/20098/5/20098/5/2009 4:04:04 PMPFAIL
The griddle/stove is not 6" behind the edge of the hood as required in the IMC. The light in the hood did not shut off on suppression system activation as per Boise City Ordinance. The manual activation station is mounted too high as per the IFC. The activation of the hood suppression system did not set off the existing fire alarm system as required per the IFC and NFPA 72. The remote annunciator and the monitoring station only showed a fire trouble signal.
FIR08-00832 INSP-Final Inspection8/5/20098/5/20098/5/2009 3:52:02 PMPFAIL
Todays inspection was for completed work in this building. Everything is complete on the second floor except for the corridor.
FIR08-00831 INSP-Final Inspection8/5/20098/5/20098/5/2009 3:50:32 PMPFAIL
Todays inspection was for completed work in this building. The first and second floor is complete except for the corridors.
FIR08-00830 INSP-Final Inspection8/5/20098/5/20098/5/2009 3:47:39 PMAFAIL
Todays inspection was for completed sprinkler work for the second and third floor areas of this building. The only areas not complete are the third floor Atrium and the second floor corridor.
BLD09-00744 FIRE-Final Inspection8/5/20098/5/20098/5/2009 2:05:05 PMPPASS
life safety passed
BLD09-00754 FIRE-Final Inspection8/5/20098/5/20098/5/2009 1:14:54 PMPPASS
life safety passed
BLD08-02057 FIRE-Final Inspection8/4/20098/5/20098/5/2009 9:54:30 AMAPASS
Life safety passed.
FIR08-00831 INSP-Sprinkler Rough-in8/4/20098/5/20098/4/2009 4:46:59 PMACANC
Duplicate inspection.