FIR09-00192
| FIR-Aging Inspection | 8/5/2010 | 8/5/2010 | 8/10/2010 2:08:52 PM | | FAIL |
|
|
|
FIR09-00429
| FIR-Aging Inspection | 8/5/2010 | 8/5/2010 | 8/5/2010 4:07:01 PM | | FAIL |
|
|
Contractor has failed to request a field inspection for work completed.
|
FIR09-00267
| FIR-Aging Inspection | 8/5/2010 | 8/5/2010 | 8/5/2010 4:04:38 PM | | FAIL |
|
|
Contractor has failed to request a field inspection for work completed.
|
FIR10-00349
| INSP-Final Inspection | 8/5/2010 | 8/5/2010 | 8/5/2010 3:53:46 PM | P | PART |
|
|
request a final inspection at Idahostel for this afternoon. Please call one hour before inspection time to ensure access into the building. Joe Snyder is the contact @ ###-####. Phone #: ###-#### >> Inspection requested via web by Trent Bice NOTE: Inspection request permit number does not match the project intended for inspection... Notified contractor.
|
FIR10-00333
| INSP-Sprinkler Rough-in/Hydro | 8/4/2010 | 8/5/2010 | 8/5/2010 3:49:41 PM | P | FAIL |
|
|
New pendent head locations at two separate offices do not match plan/ are overspaced per NFPA 13.
|
BLD10-01491
| FIRE-Conference | 8/4/2010 | 8/5/2010 | 8/5/2010 3:45:44 PM | A | DONE |
|
|
On site conference regarding the existing fire damper at the first floor lobby, project related fire alarm permit work, new door at the corridor, project schedule, etc.
|
BLD10-00550
| FIRE-Conference | 8/4/2010 | 8/5/2010 | 8/5/2010 3:38:37 PM | A | DONE |
|
|
On site conference regarding project related fire alarm work, HVAC duct detectors, light fixture obstructions at the womens restroom, door hardware, fire code review notes, type one hood suppression, seismic clearance at the new UG fire sprinkler supply, project schedule, etc.
|
BLD10-00236
| FIRE-Final Inspection | 8/4/2010 | 8/5/2010 | 8/5/2010 3:32:31 PM | A | PASS |
|
|
Fire life safety is acceptable pending signage per review notes items #3 and #7 are posted as discussed.
|
BLD09-01042
| FIRE-Final Inspection | 8/4/2010 | 8/5/2010 | 8/5/2010 3:27:41 PM | A | PASS |
|
|
Fire life safety inspection passed. Correction items finished.
|
FIR10-00232
| INSP-Final Inspection | 8/5/2010 | 8/5/2010 | 8/5/2010 3:24:36 PM | A | DEFR |
|
|
Overbooked
|