Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00192 FIR-Aging Inspection8/5/20108/5/20108/10/2010 2:08:52 PM FAIL
FIR09-00429 FIR-Aging Inspection8/5/20108/5/20108/5/2010 4:07:01 PM FAIL
Contractor has failed to request a field inspection for work completed.
FIR09-00267 FIR-Aging Inspection8/5/20108/5/20108/5/2010 4:04:38 PM FAIL
Contractor has failed to request a field inspection for work completed.
FIR10-00349 INSP-Final Inspection8/5/20108/5/20108/5/2010 3:53:46 PMPPART
request a final inspection at Idahostel for this afternoon. Please call one hour before inspection time to ensure access into the building. Joe Snyder is the contact @ ###-####. Phone #: ###-#### >> Inspection requested via web by Trent Bice NOTE: Inspection request permit number does not match the project intended for inspection... Notified contractor.
FIR10-00333 INSP-Sprinkler Rough-in/Hydro8/4/20108/5/20108/5/2010 3:49:41 PMPFAIL
New pendent head locations at two separate offices do not match plan/ are overspaced per NFPA 13.
BLD10-01491 FIRE-Conference8/4/20108/5/20108/5/2010 3:45:44 PMADONE
On site conference regarding the existing fire damper at the first floor lobby, project related fire alarm permit work, new door at the corridor, project schedule, etc.
BLD10-00550 FIRE-Conference8/4/20108/5/20108/5/2010 3:38:37 PMADONE
On site conference regarding project related fire alarm work, HVAC duct detectors, light fixture obstructions at the womens restroom, door hardware, fire code review notes, type one hood suppression, seismic clearance at the new UG fire sprinkler supply, project schedule, etc.
BLD10-00236 FIRE-Final Inspection8/4/20108/5/20108/5/2010 3:32:31 PMAPASS
Fire life safety is acceptable pending signage per review notes items #3 and #7 are posted as discussed.
BLD09-01042 FIRE-Final Inspection8/4/20108/5/20108/5/2010 3:27:41 PMAPASS
Fire life safety inspection passed. Correction items finished.
FIR10-00232 INSP-Final Inspection8/5/20108/5/20108/5/2010 3:24:36 PMADEFR
Overbooked