BLD11-00686
| FIRE-Final Inspection | 8/5/2011 | 8/5/2011 | 8/8/2011 7:37:54 AM | P | CANC |
|
|
Canceled due to inspection work load
|
FIR11-00385
| INSP-Final Inspection | 8/5/2011 | 8/5/2011 | 8/5/2011 3:58:04 PM | P | CANC |
|
|
To be canceled per Robert since the work has not been completed yet.
|
FIR11-00384
| INSP-Final Inspection | 8/5/2011 | 8/5/2011 | 8/5/2011 3:14:30 PM | P | CANC |
|
|
Permit was called in twice.
|
FIR11-00384
| INSP-Final Inspection | 8/4/2011 | 8/5/2011 | 8/5/2011 3:13:40 PM | A | FAIL |
|
|
Can't final yet but the rough-in portion is passed. The dry wall ceiling has been removed to expose the piping. So when that is done and the painting is completed this permti can be finaled.
|
FIR11-00299
| INSP-Sprinkler Rough-in | 8/5/2011 | 8/5/2011 | 8/5/2011 3:12:04 PM | P | PASS |
|
|
The under ground supply piping is ok to cover.
|
FIR11-00302
| INSP-Final Inspection | 8/4/2011 | 8/5/2011 | 8/5/2011 2:35:59 PM | P | CANC |
|
|
To be rescheduled for monday per phone conversation with colton Phone #: ###-####
|
BLD11-00080
| FIRE-Final Inspection | 8/3/2011 | 8/5/2011 | 8/5/2011 2:33:09 PM | A | PASS |
|
|
life safety passed
|
FIR11-00311
| INSP-Sprinkler Rough-in | 8/5/2011 | 8/5/2011 | 8/5/2011 2:10:16 PM | P | PART |
|
|
Sprinkler piping can be covered. I found one upright sprinkler head that has been painted that is located at the main exit.
|
BLD11-01409
| FIRE-Final Inspection | 8/5/2011 | 8/5/2011 | 8/5/2011 2:06:16 PM | P | PASS |
|
|
life safety passed
|
FIR11-00271
| INSP-Final Inspection | 8/5/2011 | 8/5/2011 | 8/5/2011 2:05:11 PM | P | PASS |
|
|
Permit finaled
|
FIR11-00246
| INSP-Final Inspection | 8/1/2011 | 8/5/2011 | 8/5/2011 1:51:34 PM | A | CANC |
|
|
Canceled due to inspection load and meeting schedule with Trent. Trent said he would reschedule for next week.
|
BLD10-01036
| FIRE-Final Inspection | 8/4/2011 | 8/5/2011 | 8/5/2011 1:23:36 PM | A | FAIL |
|
|
Need final sign off for the fire alarm permit. Also I found a manual pull station at the north exit fo the gym that is mounted too high. There are two emergency lights that need the batteries hooked up and one combo exit sign/emergency light that is located over the main exit that did not function. The exit sign from the gym back into the school is missing as well.
|
FIR11-00038
| INSP-Final Inspection | 8/4/2011 | 8/5/2011 | 8/5/2011 1:14:34 PM | A | FAIL |
|
|
No inspection was performed due to signal reports not being provided as required per the fire alarm plan review general comments. A correction notice was left with Jerry, the job site superintendant.
|
FIR11-00161
| INSP-Sprinkler Rough-in | 8/4/2011 | 8/5/2011 | 8/5/2011 11:40:43 AM | A | PART |
|
|
The underground supply line piping has not been connected to the United Water supply outlet. The underground supply piping is ok to cover from the cap near the United Water connection point to the 2" PIV which is located just off of the front porch.
|
BLD11-00631
| FIRE-Final Inspection | 8/4/2011 | 8/5/2011 | 8/5/2011 11:38:22 AM | A | FAIL |
|
|
Fire sprinkler and fire alarm permits will be required for the under spaced sprinkler pendants and the over spaced strobes. All other items appeared ok.
|
BLD11-01089
| FIRE-Final Inspection | 7/7/2011 | 8/5/2011 | 8/5/2011 11:36:32 AM | A | PASS |
|
|
Life safety passed
|
BLD11-01379
| FIRE-Final Inspection | 8/4/2011 | 8/5/2011 | 8/5/2011 9:27:45 AM | A | PASS |
|
|
life safety passed
|
FIR11-00360
| INSP-Final Inspection | 8/5/2011 | 8/5/2011 | 8/5/2011 9:26:22 AM | P | PASS |
|
|
Permit finaled
|
FIR11-00230
| INSP-Final Inspection | 8/4/2011 | 8/5/2011 | 8/5/2011 8:19:47 AM | A | CANC |
|
|
Meet in the plan review room B.25 Phone #: ###-#### >> Inspection requested via web by John Wheeler Inspection cancelled from web by: John Wheeler
|