Inspections for the day of: Friday, August 5, 2011.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-00686 FIRE-Final Inspection8/5/20118/5/20118/8/2011 7:37:54 AMPCANC
Canceled due to inspection work load
FIR11-00385 INSP-Final Inspection8/5/20118/5/20118/5/2011 3:58:04 PMPCANC
To be canceled per Robert since the work has not been completed yet.
FIR11-00384 INSP-Final Inspection8/5/20118/5/20118/5/2011 3:14:30 PMPCANC
Permit was called in twice.
FIR11-00384 INSP-Final Inspection8/4/20118/5/20118/5/2011 3:13:40 PMAFAIL
Can't final yet but the rough-in portion is passed. The dry wall ceiling has been removed to expose the piping. So when that is done and the painting is completed this permti can be finaled.
FIR11-00299 INSP-Sprinkler Rough-in8/5/20118/5/20118/5/2011 3:12:04 PMPPASS
The under ground supply piping is ok to cover.
FIR11-00302 INSP-Final Inspection8/4/20118/5/20118/5/2011 2:35:59 PMPCANC
To be rescheduled for monday per phone conversation with colton Phone #: ###-####
BLD11-00080 FIRE-Final Inspection8/3/20118/5/20118/5/2011 2:33:09 PMAPASS
life safety passed
FIR11-00311 INSP-Sprinkler Rough-in8/5/20118/5/20118/5/2011 2:10:16 PMPPART
Sprinkler piping can be covered. I found one upright sprinkler head that has been painted that is located at the main exit.
BLD11-01409 FIRE-Final Inspection8/5/20118/5/20118/5/2011 2:06:16 PMPPASS
life safety passed
FIR11-00271 INSP-Final Inspection8/5/20118/5/20118/5/2011 2:05:11 PMPPASS
Permit finaled
FIR11-00246 INSP-Final Inspection8/1/20118/5/20118/5/2011 1:51:34 PMACANC
Canceled due to inspection load and meeting schedule with Trent. Trent said he would reschedule for next week.
BLD10-01036 FIRE-Final Inspection8/4/20118/5/20118/5/2011 1:23:36 PMAFAIL
Need final sign off for the fire alarm permit. Also I found a manual pull station at the north exit fo the gym that is mounted too high. There are two emergency lights that need the batteries hooked up and one combo exit sign/emergency light that is located over the main exit that did not function. The exit sign from the gym back into the school is missing as well.
FIR11-00038 INSP-Final Inspection8/4/20118/5/20118/5/2011 1:14:34 PMAFAIL
No inspection was performed due to signal reports not being provided as required per the fire alarm plan review general comments. A correction notice was left with Jerry, the job site superintendant.
FIR11-00161 INSP-Sprinkler Rough-in8/4/20118/5/20118/5/2011 11:40:43 AMAPART
The underground supply line piping has not been connected to the United Water supply outlet. The underground supply piping is ok to cover from the cap near the United Water connection point to the 2" PIV which is located just off of the front porch.
BLD11-00631 FIRE-Final Inspection8/4/20118/5/20118/5/2011 11:38:22 AMAFAIL
Fire sprinkler and fire alarm permits will be required for the under spaced sprinkler pendants and the over spaced strobes. All other items appeared ok.
BLD11-01089 FIRE-Final Inspection7/7/20118/5/20118/5/2011 11:36:32 AMAPASS
Life safety passed
BLD11-01379 FIRE-Final Inspection8/4/20118/5/20118/5/2011 9:27:45 AMAPASS
life safety passed
FIR11-00360 INSP-Final Inspection8/5/20118/5/20118/5/2011 9:26:22 AMPPASS
Permit finaled
FIR11-00230 INSP-Final Inspection8/4/20118/5/20118/5/2011 8:19:47 AMACANC
Meet in the plan review room B.25 Phone #: ###-#### >> Inspection requested via web by John Wheeler Inspection cancelled from web by: John Wheeler