Inspections for the day of: Wednesday, August 5, 2015.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-03246 Electrical Rough-In8/4/20158/5/20158/5/2015 2:25:54 PMPPASS
Levi. Tower 3 floor #2 final. Phone #: ###-#### Inspection requested via web by Sean DeLacy final ok on rms. 210 thru 215. Also corrections made final ok rms. 313 and 314
ELE15-02131 Final8/5/20158/5/20158/5/2015 1:12:59 PMPNR
Final inspections units 2nd floor. Phone #: ###-#### Inspection requested via web by Rafael Castillo dishwashers not in yet
ELE15-02132 Final8/5/20158/5/20158/5/2015 1:10:42 PMPNR
Final inspections units 2nd floor. Phone #: ###-#### Inspection requested via web by Rafael Castillo dishwashers not in yet
ELE15-02132 Final8/5/20158/5/20158/5/2015 1:05:45 PMAPART
Final inspections units 2nd floor. Phone #: ###-#### Inspection requested via web by Rafael Castillo final ok rms. 221, 224 thru 231, 232 thru 241. exterior receptacles not done in rms. 200, 218, 223 and 233. All rooms still need 50% energy efficient lamps.
ELE15-02131 Final8/5/20158/5/20158/5/2015 12:59:20 PMAPART
Final inspections 2nd floor units. Phone #: ###-#### Inspection requested via web by Rafael Castillo final ok on rms. 221, 224 thru 231, 232 thru 241 NOTE; o/s receptacles not done in rms. 200, 218,223 and 233 also need 50% energy effiecient lamps throughout.
ELE14-01963 Electrical Rough-In8/5/20158/5/20158/5/2015 12:29:45 PMAPASS
Garage ceiling grid inspection west wing. Phone #: ###-#### Inspection requested via web by Rafael Castillo r/i ok t bar ceiling west see e sheets
ELE15-02352 Temporary Service8/4/20158/5/20158/5/2015 9:34:54 AMAFAIL
Richard Phone #: ###-#### minimum 6x6 post as per Idaho Power Co.
ELE15-02410 Final8/4/20158/5/20158/5/2015 9:15:53 AMAFAIL
Inspection requested via web by Cindie Swaim 110.16- arc flash hazard warning label required on loadcenters. 110.24- service equipment in other than dwellings shall be legibly marked in the field with the maximum available fault current including date of calculation and be of suffiecient durability. ( from Idaho Power). 250 53(D)(2)- supplemental ground rod required. 250.94-intersystem bond termiation required. 250.104(A)- Bond water pipes or sections where required. Also need to call for "permanent service " when ready, then final. No phone number or contact to call
ELE15-02161 Electrical Rough-In8/4/20158/5/20158/5/2015 8:30:12 AMAPASS
underground - late morning please Thank you Phone #: ###-#### Inspection requested via web by Celinda Winters r/i underslab 100 % ok