ELE15-02740
| Electrical Rough-In | 8/5/2016 | 8/5/2016 | 8/5/2016 2:24:13 PM | P | PASS |
|
|
Seth Phone #: ###-#### Kitchen grid and front covered entrance lid rough in ok cover
|
ELE16-02487
| Permanent Service | 8/3/2016 | 8/5/2016 | 8/5/2016 1:58:45 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Craig Korell Range and dryer changed. Will call for final when labelled. p/s o/h rec ok
|
ELE16-01628
| Electrical Rough-In | 8/4/2016 | 8/5/2016 | 8/5/2016 1:39:37 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Kitchen area grid rough in ok cover
|
ELE16-02072
| Final | 8/5/2016 | 8/5/2016 | 8/5/2016 1:04:20 PM | P | PASS |
|
|
Contractor moved vent pipe installed in front of electrical service. Site ready for re-inspection. Russell Steadman is contact @ ###-####. Phone #: ###-#### Inspection requested via web by Todd Alder Final ok
|
ELE16-02546
| Conference | 8/4/2016 | 8/5/2016 | 8/5/2016 12:39:57 PM | P | DONE |
|
|
James Phone #: ###-#### Discussed flipping panel around in wall and will be in dining area. Master bed and bath addition talked receptacle spacing, tamper resistant type, bathroom recept.20 amp dedicated, light over shower wet location rated, outdoor recept type and cover.
|
ELE15-03478
| Final | 8/5/2016 | 8/5/2016 | 8/5/2016 12:08:35 PM | P | PASS |
|
|
corrections have been made Phone #: ###-#### Inspection requested via web by Shaun Kirkman Final ok
|
ELE16-02544
| Rough-In Permanent Service | 8/4/2016 | 8/5/2016 | 8/5/2016 11:26:10 AM | A | PASS |
|
|
Any questions please let me know, thx,. TW Phone #: ###-#### Inspection requested via web by Stephen Kren Rough in ok cover p/s o/h n ok
|
MIS16-00249
| ELE-Conference | 8/4/2016 | 8/5/2016 | 8/5/2016 10:39:22 AM | A | FAIL |
|
|
work being done without a permit per Eric Strole New wiring installed in kitchen area and both basement and upstair of back split level. Double fee applied. Individuals working in kitchen area on granite ordered to leave.
|
ELE16-02532
| Electrical Rough-In | 8/3/2016 | 8/5/2016 | 8/5/2016 10:21:06 AM | A | PART |
|
|
ready for rough. supposed to be open. Phone #: ###-#### Inspection requested via web by Kelly Felin Receptacle added for hospital bed location in bed room. 2 boxes located over tub area junction points only and shall have nonmetallic cover wet location rated. Bathroom rough in ok cover
|
ELE16-01207
| Conference | 8/4/2016 | 8/5/2016 | 8/5/2016 9:53:26 AM | A | DONE |
|
|
John Phone #: ###-#### Discussed electrical room layout, work space and dedicated electrical space OK. Discussed if installation of occ sensors in multiple locations on flourescent fixtures all inter connected and used as wireway. Installation of occ sensors OK
|
ELE16-01652
| Electrical Rough-In | 8/4/2016 | 8/5/2016 | 8/5/2016 9:24:06 AM | A | PASS |
|
|
Underground East Side of North Spur. AM early please. Phone #: ###-#### Inspection requested via web by Kristopher Wilson Area as noted underground rough in ok cover
|
ELE15-03901
| Electrical Rough-In | 8/4/2016 | 8/5/2016 | 8/5/2016 9:23:13 AM | A | PART |
|
|
Call Rafael for pre-walk final inspection of the 5th floor. Phone #: ###-#### Inspection requested via web by Rafael Castillo 400.8- Flexible cord shall not penetrate walls. 300.21- Seal fire wall penetrations. 300.25- all boxes shall have covers. LV boxes. 406.6- Server rm receptacle plates shall seat to mounting surface. Temp final ok
|
ELE12-00850
| ELE-Aging Inspection | 8/5/2016 | 8/5/2016 | 8/5/2016 6:45:29 AM | | CANC |
|
|
|