Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-02328 ELE-Aging Inspection8/5/20168/5/20168/12/2016 8:00:05 AM CANC
too busy
ELE16-02417 Conference8/5/20168/5/20168/5/2016 2:29:14 PMPDONE
Mitch Phone #: ###-####
discussed code requiremnets for dental offices and patient care areas to be pulled in redundent ground
ELE16-02554 Electrical Rough-In8/5/20168/5/20168/5/2016 1:27:19 PMPPASS
Phone #: ###-#### Inspection requested via web by Don Conley
portin of fire damage ok cover(kitchen&front room)
ELE16-02554 Permanent Service8/5/20168/5/20168/5/2016 1:23:32 PMPFAIL
Phone #: ###-#### Inspection requested via web by Don Conley
230.71 shall not have more then 6 service disconnecting means
230.70 shall provide means of service disconnecting
ELE14-00007 Final8/4/20168/5/20168/5/2016 11:47:24 AMAPASS
Bob
there is access to this place 10 to 2 just pull up to gate and push the button
call me with any issues.
the generator is down the steps to your rights from the service gear.
Phone #: ###-#### Inspection requested via web by Mike Cole
final for generator ok
ELE15-02641 Electrical Rough-In8/4/20168/5/20168/5/2016 11:05:16 AMAPASS
6th Floor Phone #: ###-#### Inspection requested via web by Kerri Hamilton
6th floor hard lids above all units and 1 little hall drop only ok cover
ELE16-00442 Electrical Rough-In8/4/20168/5/20168/5/2016 10:52:45 AMAPASS
Jake Phone #: ###-####
3rd and 4th corrridor walls and cieling only ok cover. Discussed with GC that all water lines and equipment within 6' above panels shall not be there and will remove what is in the dedicated area.
ELE16-02415 Rough-In Permanent Service8/5/20168/5/20168/5/2016 10:46:47 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
rough-in ok cover p/s u/g n ok
ELE16-02540 Final8/4/20168/5/20168/5/2016 10:16:36 AMAPASS
Please contact Greg Critchfield for exact location....###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce
final for washer and dryers ok
ELE16-02143 Electrical Rough-In8/4/20168/5/20168/5/2016 9:18:06 AMAPASS
Rough-In Inspection for walls and ceilings in Bathrooms.
Contact Marshall Dobson @ ###-####
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
5th floor hard lids in baths only ok cover
ELE16-02256 Electrical Rough-In8/4/20168/5/20168/5/2016 8:58:24 AMACANC
existing service feeding out buildings. contact on this job site is Brandon G. at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce
needed p/s
ELE16-02256 Permanent Service8/5/20168/5/20168/5/2016 8:57:48 AMPPASS
existing service feeding out buildings. contact on this job site is Brandon G. at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce
p/s u/g n ok
ELE16-01732 Final8/5/20168/5/20168/5/2016 8:40:59 AMPPASS
as per James Ady final ok
ELE16-02399 Electrical Rough-In8/4/20168/5/20168/4/2016 11:57:03 AMPPASS
Underground Phone #: ###-#### Inspection requested via web by Christy Cheney
u/g as noted on contractors print ok cover