Inspections for the day of: Friday, August 5, 2016.
Number of inspections: 26
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorChad Schwendiman
TitleMEC-INSPECTOR
Phone #780-9549
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC16-03509 Pressure Test8/5/20168/5/20168/5/2016 2:22:32 PMPPASS
Phone #: ###-#### Inspection requested via web by Troy Worley - 20lb gas pass
MEC16-03509 Rough-in8/5/20168/5/20168/5/2016 2:22:13 PMPFAIL
Phone #: ###-#### Inspection requested via web by Troy Worley - need approved manual J on site, exhaust fans haven't been installed yet, 4"x10"x7" boots are undersized for cfm's
MEC16-03502 Final8/5/20168/5/20168/5/2016 1:49:34 PMPPASS
Would like early PM. and call when on way. Thank you! Phone #: ###-#### Inspection requested via web by Xanti Berria
MEC16-02773 Final8/5/20168/5/20168/5/2016 1:29:27 PMPFAIL
Still missing the air balance report
MEC16-03333 Rough-in8/5/20168/5/20168/5/2016 1:07:02 PMPPASS
thank you Phone #: ###-#### Inspection requested via web by Randy Hart
MEC16-02258 Rough-in8/4/20168/5/20168/5/2016 11:31:31 AMAPART
ceiling cover in kitchen Phone #: ###-#### Inspection requested via web by Brandon Sorensen - okay to cover grid ceiling in the kitchen except for in front of the kitchen hood
MEC16-01853 Pressure Test8/4/20168/5/20168/5/2016 11:30:26 AMAPART
Mechanical Gas Pressure Test. If you have any questions please contact Jerry @ ###-#### Phone #: ###-#### Inspection requested via web by Stacia Haumann - 20lb gas pass on the cook line
MEC16-02839 Final8/4/20168/5/20168/5/2016 11:14:10 AMAPASS
Call Luke Fine for access. Phone #: ###-#### Inspection requested via web by David Tully
MEC16-03482 Final8/4/20168/5/20168/5/2016 10:52:45 AMAPASS
Can you please schedule the inspection for sometime between 9:30 AM to 11:30 AM. Please contact the property owner for access. Tom Smith. Ph# ###-####. Thank you. Phone #: ###-#### Inspection requested via web by David Lamoreaux
MEC16-03420 Rough-in8/5/20168/5/20168/5/2016 10:47:40 AMPPASS
Phone #: ###-#### Inspection requested via web by Dan Otero
MEC16-03507 Final8/4/20168/5/20168/5/2016 10:12:48 AMAPASS
It''s on the right side of the house in the back. Phone #: ###-#### Inspection requested via web by Sean Hyten - 20lb gas pass on 3 underground lines
MEC16-03353 Rough-in8/4/20168/5/20168/5/2016 9:52:43 AMPCANC
Please call Aaron with any questions! Phone #: ###-#### >> Inspection requested via web by john shay Inspection cancelled from web by: john shay
MEC16-03069 Rough-in8/4/20168/5/20168/5/2016 9:12:23 AMAFAIL
Phone #: ###-#### Inspection requested via web by Rick Montgomery - previous corrections have not been made. still need to insulate bare metal in exterior soffit
MEC16-03171 Rough-in8/3/20168/5/20168/5/2016 8:38:46 AMAPART
Inspection of refrigerant on 1st floor Phone #: ###-#### Inspection requested via web by patrick graves - refrigerant piping okay in 1st floor
MIS16-00249 MEC-Conference8/4/20168/5/20168/5/2016 8:21:05 AMAFAIL
work being done without a permit per Eric Strole - Work being performed with out a permit. Need to get mechanical permit. Double fee on permit
MEC16-01892 Rough-in8/4/20168/5/20168/5/2016 8:19:08 AMAPART
Brian ###-####/ Pharmacy rough in Phone #: ###-#### Inspection requested via web by Crystal Grant - okay to cover pharmacy area
MEC16-03333 Rough-in8/3/20168/5/20168/5/2016 7:55:00 AMAFAIL
Phone #: ###-#### Inspection requested via web by Randy Hart - need approved manual J on site
MEC16-03389 Pressure Test8/4/20168/5/20168/5/2016 7:33:17 AMAFAIL
Phone #: ###-#### Inspection requested via web by Troy Worley - Gauge won't zero out
MEC16-03389 Rough-in8/4/20168/5/20168/5/2016 7:32:48 AMAFAIL
Phone #: ###-#### Inspection requested via web by Troy Worley - exhaust fans are not connected, 4"x10"x7" boots are undersized for the designed cfm's
MEC16-02091 Final8/4/20168/5/20168/5/2016 7:10:48 AMAPASS
Please call Roger ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss
MEC16-03442 Final8/4/20168/5/20168/5/2016 7:00:20 AMAPASS
GAS PRESSURE CHECK Phone #: ###-#### Inspection requested via web by Monica Lindsay - 20lb gas pass
MEC16-00799 Final8/4/20168/5/20168/5/2016 6:42:22 AMAPART
Partial final 5th floor. Onsite contact: Jim Brown Phone #: ###-#### Inspection requested via web by Melissa Kaae - temporary occupancy okay for showers on 5th floor and beta bar on 5th floor
MEC15-02759 Rough-in8/4/20168/5/20168/5/2016 6:41:23 AMAPART
Early AM grease duct light test 4th floor. Approved by Bill VanDegrift ; Chad Schwendiman. Onsite contact: Jim Brown. Phone #: ###-#### Inspection requested via web by Melissa Kaae -grease duct light test pass on 4th floor from shaft up to roof curbs of gbad
MEC15-00207 Mec-Aging Inspection8/5/20168/5/20168/5/2016 5:41:38 AM CANC
MEC15-02784 Mec-Aging Inspection8/5/20168/5/20168/5/2016 5:41:28 AM DONE
Expired
MEC15-02784 DOC - Permit Expired8/5/20168/5/20168/5/2016 5:41:12 AMAPASS