Inspections for the day of: Friday, August 5, 2016.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00344 INSP-Sprinkler Rough-in/Hydro8/5/20168/5/20168/5/2016 2:24:25 PMPPASS
24 hour air test for new dry system passed/complete
FIR16-00362 INSP-Final Inspection8/5/20168/5/20168/5/2016 12:30:03 PMPPART
Final fire alarm inspection complete, audio visual device in south cooler did not operate, will verify A/V has been repaired during commercial hood suppression inspection.
FIR16-00492 INSP-Final Inspection8/5/20168/5/20168/5/2016 11:21:01 AMPPASS
Final fire alarm inspection passed/complete
FIR16-00327 INSP-Sprinkler Rough-in8/4/20168/5/20168/5/2016 11:20:37 AMACANC
Inspection request rescheduled due to access issues, inspection will be completed on 08AUG2016
BLD16-00003 FIRE-Final Inspection8/4/20168/5/20168/5/2016 10:22:13 AMAPASS
Previously noted items have been corrected, noted that some of the interior doors have existing round knob type door hardware, no fire sprinklers, no fire alarms, fire extinguishers are in place with current inspection tags. Final life fire safety inspection complete.
FIR15-00900 INSP-Supply line flush8/4/20168/5/20168/5/2016 10:03:49 AMAFAIL
Could not verify if fire line is connected or not, flush could not be accomplished.