Inspections for the day of: Wednesday, August 5, 2020.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-01300 Electrical Rough-In8/3/20208/5/20208/5/2020 2:17:06 PMPFAIL
Screened- Leslie- Please call access Phone #: ###-####...

1) wiring methods for romex shall be to code
stapling, cable laid flat, use of stack its where more than 3 wires, distance from edge of stud
wiring thru attic above rafters/trusses
ELE20-01300 Permanent Service8/5/20208/5/20208/5/2020 2:10:10 PMPPASS
Screened- Leslie- Please call access Phone #: ###-####...
p/s o/h new ok
ELE20-02655 Permanent Service8/5/20208/5/20208/5/2020 1:34:45 PMPPASS
Relocate 200 Service Phone #: ###-#### Inspection requested via web by Emmet Bushman....
moving all-in-one to corner of house...grounding brought up to code
p/s o/h ok to move
ELE20-02591 Electrical Rough-In8/4/20208/5/20208/5/2020 12:23:37 PMPPASS
Devon Lewno will be the onsite contact - ###-#### Phone #: ###-#### Inspection requested via web by BRS Permitting...
UL listings and plans onsite
access side of house for final
ELE20-01870 Permanent Service8/5/20208/5/20208/5/2020 11:46:59 AMPPASS
Phone #: ###-#### Inspection requested via web by kendall bender...
p/s u/g new ok
ELE20-02686 Final7/31/20208/5/20208/5/2020 11:28:40 AMPPASS
If you have questions please call Todd ###-#### Phone #: ###-#### Inspection requested via web by Kendra Lanham...complete..GFCI protection...ok to final
ELE20-02750 Electrical Rough-In8/4/20208/5/20208/5/2020 10:33:24 AMACANC
Dan Cromie is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce...wrong inspection...in future please schedule permanent service inspection
ELE20-02750 Permanent Service8/5/20208/5/20208/5/2020 10:32:32 AMAPASS
Dan Cromie is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce....
service only inspection...2 ground rods verified
at Meyers cabinet and pull box
p/s u/g new ok
ELE20-02756 Final8/4/20208/5/20208/5/2020 10:03:24 AMAPASS
Phone #: ###-#### Inspection requested via web by Jason Gaythwaite...
due to access inspection done by images...sealtite from exterior rated junction box to disconnect with fused protection...ok to final...complete
ELE20-02761 Conference8/4/20208/5/20208/5/2020 9:49:35 AMAPASS
Haley -*/Screened*/ Phone #: ###-####...
discussed wiring of 20A 120v circuit...GFCI protection, in-use heavyduty cover, weather resistant and tamper resistant, junction boxes accesibility...homeowners father-in-law helping and very competent in work
ELE20-02761 Electrical Rough-In8/5/20208/5/20208/5/2020 9:44:21 AMAPASS
Haley -*/Screened*/ Phone #: ###-####....
pipe/trench ok to cover
ELE20-02672 Electrical Rough-In7/30/20208/5/20208/5/2020 9:14:45 AMAPASS
crew will be onsite thank you! Phone #: ###-#### Inspection requested via web by Terissa Morain....
UL listings verified and plans onsite
ELE20-01992 Final8/4/20208/5/20208/5/2020 9:00:44 AMAPASS
Lock box code 8607 Phone #: ###-#### Inspection requested via web by Ryan Wake...
ok to final...card signed
ELE19-02270 Final8/4/20208/5/20208/5/2020 8:45:29 AMAPASS
Phone #: ###-#### Inspection requested via web by Danny Pardee...
UL label and disconnect present...ok to final
ELE20-02699 Temporary Service8/4/20208/5/20208/5/2020 8:23:57 AMAPASS
Phone #: ###-#### Inspection requested via web by Troy Ballard...
t/s u/g new ok