Inspections for the day of: Wednesday, August 5, 2020.
Number of inspections: 29
Percentage of inspections complete: 83 %
Percentage of inspections not complete: 17 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR20-00146 INSP-Sprinkler Rough-in/Hydro8/5/20208/5/20208/5/2020 6:36:47 PMPPART
Hydrostatic test for underground supply witnessed with no pressure loss observed at riser provided gauge.

Phone #: ###-#### Inspection requested via web by Lonnie Greenfield
FIR19-00804 INSP-Sprinkler Rough-in8/5/20208/5/20208/5/2020 6:36:46 PMPPART
Rough to cover inspection for overhead fire sprinkler piping above restroom hardlids 2 through 9 complete, restroom hardlids 2 through 9 approved for cover.

Inspections for rough to cover in bathrooms, floors 2-9. Phone #: ###-#### Inspection requested via web by Daniel Buccino
BLD20-01180 FIRE-Final Inspection8/5/20208/5/20208/5/2020 2:07:21 PMPPASS
No fire sprinklers, no fire alarms, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection is complete, signature provided on permit sign off card.

screened // Bob Phone #: ###-####
BLD20-02608 FIRE-Final Inspection8/5/20208/5/20208/5/2020 2:06:23 PMPFAIL
Install exit signage and emergency lighting, to include exit discharge landing to public way, on level 1 as shown on city approved documents. Fire sprinkler modifications in basement level will be required, room being used as storage has sprinkler heads overspaced for ordinary hazard, two areas will require sprinkler heads to be added. Wires are attached to the fire sprinkler piping, per NFPA13 no external loads shall be applied to fire sprinkler piping. Fire sprinkler head in basement bathroom is painted, per NFPA13 the fire sprinkler head will required to be replaced. Any and all modifications to the fire sprinkler system will require a seperate permit. Provide fire extinguisher for basement level.

screened // Tanya Phone #: ###-####
BLD20-02663 FIRE-Final Inspection8/5/20208/5/20208/5/2020 2:00:45 PMPFAIL
Provide annual inspection on fire sprinkler backflow, test tag on backflow is from 2017, backflow must be tested annually.

screened // Tanya Phone #: ###-####
FIR20-00121 INSP-Final Inspection8/4/20208/5/20208/5/2020 12:17:08 PMAPASS
Final fire sprinkler inspection is complete, irrigation shutoff witnessed during flow switch activation.

Phone #: ###-#### Inspection requested via web by Jonathan Lee
FIR20-00135 INSP-Final Inspection8/4/20208/5/20208/5/2020 12:16:45 PMAPASS
Final fire sprinkler inspection is complete, irrigation shutoff witnessed during flow switch activation.

Phone #: ###-#### Inspection requested via web by Jonathan Lee
FIR20-00133 INSP-Final Inspection8/4/20208/5/20208/5/2020 12:16:26 PMAPASS
Final fire sprinkler inspection is complete, irrigation shutoff witnessed during flow switch activation.

Phone #: ###-#### Inspection requested via web by Jonathan Lee
FIR20-00130 INSP-Final Inspection8/4/20208/5/20208/5/2020 12:16:09 PMAPASS
Final fire sprinkler inspection is complete, irrigation shutoff witnessed during flow switch activation.

Phone #: ###-#### Inspection requested via web by Jonathan Lee
FIR20-00129 INSP-Final Inspection8/4/20208/5/20208/5/2020 12:15:46 PMAPASS
Final fire sprinkler inspection is complete, irrigation shutoff witnessed during flow switch activation.

Phone #: ###-#### Inspection requested via web by Jonathan Lee
FIR20-00129 INSP-Sprinkler Rough-in/Hydro8/4/20208/5/20208/5/2020 12:14:24 PMADONE
Hydrostatic test witnessed at city pressure with no pressure loss observed at riser provided gauge.

Phone #: ###-#### Inspection requested via web by Jonathan Lee
FIR20-00130 INSP-Sprinkler Rough-in/Hydro8/4/20208/5/20208/5/2020 12:14:13 PMADONE
Hydrostatic test witnessed at city pressure with no pressure loss observed at riser provided gauge.

Phone #: ###-#### Inspection requested via web by Jonathan Lee
FIR20-00133 INSP-Sprinkler Rough-in/Hydro8/4/20208/5/20208/5/2020 12:14:04 PMADONE
Hydrostatic test witnessed at city pressure with no pressure loss observed at riser provided gauge.

Phone #: ###-#### Inspection requested via web by Jonathan Lee
FIR20-00135 INSP-Sprinkler Rough-in/Hydro8/4/20208/5/20208/5/2020 12:13:52 PMADONE
Hydrostatic test witnessed at city pressure with no pressure loss observed at riser provided gauge.

Phone #: ###-#### Inspection requested via web by Jonathan Lee
FIR20-00121 INSP-Sprinkler Rough-in/Hydro8/4/20208/5/20208/5/2020 12:13:24 PMADONE
Hydrostatic test witnessed at city pressure with no pressure loss observed at riser provided gauge.

Phone #: ###-#### Inspection requested via web by Jonathan Lee
FIR20-00434 INSP-Sprinkler Rough-in/Hydro8/5/20208/5/20208/5/2020 12:04:42 PMAFAIL
System could not have hydro performed, cap above furnace closet was cut and removed by others, a re-hydro will be required after repair is made.
FIR20-00426 INSP-Sprinkler Rough-in8/4/20208/5/20208/5/2020 12:01:01 PMAPASS
All tenting in place at time of inspection, cover is approved. Cover sticker has been placed.

tenting Phone #: ###-#### Inspection requested via web by Jonathan Lee
FIR20-00425 INSP-Sprinkler Rough-in8/4/20208/5/20208/5/2020 12:00:45 PMAPASS
All tenting in place at time of inspection, cover is approved. Cover sticker has been placed.

tenting Phone #: ###-#### Inspection requested via web by Jonathan Lee
FIR20-00435 INSP-Sprinkler Rough-in8/4/20208/5/20208/5/2020 12:00:29 PMAPASS
All tenting in place at time of inspection, cover is approved. Cover sticker has been placed.

tenting Phone #: ###-#### Inspection requested via web by Jonathan Lee
FIR20-00143 INSP-Sprinkler Rough-in8/4/20208/5/20208/5/2020 8:42:58 AMAPASS
Rough to cover inspection for scope of work is complete, cover is approved. Fire sprinkler head to be added above cooler to cover exposed combustible material, will verify head addition on next inspection.

Tony Cetani is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
BLD20-01684 FIRE-Final Inspection8/4/20208/5/20208/5/2020 7:59:19 AMAPART
Previously noted items have been corrected, fire alarm modification to be completed under FIR20-00530 (addition of one notification devoce in changing room), fire sprinkler inspection complete, fire extingiusher is placed with a current inspection tag. 30 day TCO authorized for life fire safety, final signature contingent upon fire alarm modifications being completed and inspected.

Nicole Phone #: ###-####
FIR20-00129 INSP-Final Inspection8/4/20208/5/20208/4/2020 8:18:11 AMACANC
Phone #: ###-#### >> Inspection requested via web by Jonathan Lee Inspection cancelled from web by: Jonathan Lee
FIR20-00121 INSP-Sprinkler Rough-in/Hydro8/4/20208/5/20208/4/2020 8:17:52 AMACANC
Phone #: ###-#### >> Inspection requested via web by Jonathan Lee Inspection cancelled from web by: Jonathan Lee
FIR20-00121 INSP-Final Inspection8/4/20208/5/20208/4/2020 8:17:46 AMACANC
Phone #: ###-#### >> Inspection requested via web by Jonathan Lee Inspection cancelled from web by: Jonathan Lee
FIR12-00739 FIR-Aging Inspection8/5/20208/5/2020   
FIR12-00740 FIR-Aging Inspection8/5/20208/5/2020   
FIR13-00119 FIR-Aging Inspection8/5/20208/5/2020   
FIR14-00085 FIR-Aging Inspection8/5/20208/5/2020   
FIR14-00372 FIR-Aging Inspection8/5/20208/5/2020