Inspections for the day of: Tuesday, August 6, 2002.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-02436 Final8/2/20028/6/20028/6/2002 12:00:00 AMAFAIL
###-#### cor. posted called no violations to be retained manufactures breaker only
(sub panel) install cable clamp, and seal K Os and isolate grds and nuetrals shall either grd, or bond as 250.52,and 104, protect emt in earth,and bond it or replace with #80 PVC 8/6/2002 6:36:21 PM
ELE02-02295 Permanent Service8/2/20028/6/20028/6/2002 12:00:00 AMAPASS
###-#### meter for space #106 ok 8/6/2002 11:26:48 AM
ELE02-02446 Rough-In Permanent Service8/2/20028/6/20028/6/2002 12:00:00 AMAFAIL
###-#### cor. posted called 300.4(D) 11/4 inches,300.14 6 inches free length 210.52(B) formal dinning rm shall be on small appliance branch circuit, 210.52 (D) outlet within 3ft of both sinks M bath, 110.14 (B) all splices shall be made up tight grd wires, 110.12(A) seal, or replace plastic boxes with unused K Os, 11.3(B) replace 2,3,4 gang boxes with broken internal clamps, move jbox for j tub so it is accessible 8/6/2002 3:10:24 PM
ELE02-01458 Electrical Rough-In8/5/20028/6/20028/6/2002 12:00:00 AMAPART
TOM; Phone #: ###-#### walls tete marketing rm 8/6/2002 1:11:27 PM
ELE02-01301 Permanent Service8/5/20028/6/20028/6/2002 12:00:00 AMADONE
Scheduled by a contractor via Hello! on 08/05/2002 at 15:24:34. Contact: ###-####. see added final 8/6/2002 12:05:24 PM
ELE02-01301 Final8/6/20028/6/20028/6/2002 12:00:00 AMAFAIL
cor. posted called 210.8 gfci all recepts in bathrm, 406.4(D) , and no power too all recepts
ELE02-02463 Final8/6/20028/6/20028/6/2002 12:00:00 AMPPASS
susie wall sign for the quilt crossing; Phone #: ###-#### ok card signed 08/05/02 when Alloway called for final 8/6/2002 4:14:20 PM
ELE02-01946 Final8/6/20028/6/20028/6/2002 12:00:00 AMPFAIL
###-#### DAVID not ready called needs shelves in clothes closet so I can check for clearence, and mount outside WP cover for horizontal plane everything else checked out OK

8/6/2002 6:52:20 PM
ELE02-02034 Rough-In Permanent Service8/6/20028/6/20028/6/2002 12:00:00 AMPPASS
steve ; Phone #: ###-#### r/i ok

p/s u/g new ok 8/6/2002 7:12:08 PM
ELE02-00608 Permanent Service8/6/20028/6/20028/6/2002 12:00:00 AMPFAIL
cor. , and $45.00 reinspection fee due posted called left message 300.10, and 14 use locknuts inside and outside of cabinets and boxes where rigid conduit is used , bond bushings where R E washers are used, 250.8 no sheet metal screws for bonding ,and grounding, 344.46 bushing for rigid nipples, 250.24 connect grd and nuetrals at p/s 250.28(A) install bond screws 8/6/2002 5:48:41 PM
ELE02-02242 Electrical Rough-In8/5/20028/6/20028/6/2002 12:00:00 AMPPART
###-#### john walls pharmacy 8/6/2002 4:13:28 PM