FIR07-00627
| INSP-Final Inspection | 8/3/2007 | 8/6/2007 | 8/8/2007 1:02:47 PM | A | FAIL |
|
|
Location of the new heat detector is not approved.
|
FIR07-00636
| INSP-Final Inspection | 8/6/2007 | 8/6/2007 | 8/8/2007 8:37:52 AM | P | PASS |
|
|
Fire sprinkler system modifications completed satisfactory, permit finaled.
|
BLD07-00581
| FIRE-Final Inspection | 8/6/2007 | 8/6/2007 | 8/6/2007 4:32:54 PM | P | PASS |
|
|
Life safety inspection passed.
|
FIR07-00526
| INSP-Final Inspection | 8/6/2007 | 8/6/2007 | 8/6/2007 3:50:37 PM | P | PASS |
|
|
c/n items verified for completion, fire sprinkler permit finaled.
|
BLD07-01043
| FIRE-Conference | 8/6/2007 | 8/6/2007 | 8/6/2007 3:48:51 PM | P | DONE |
|
|
On site visit to discuss exit signage requirements, noted on approved plans two locations missing exit signs.
|
BLD07-00047
| FIRE-Final Inspection | 8/6/2007 | 8/6/2007 | 8/6/2007 3:45:48 PM | P | PASS |
|
|
Required corrections are complete, fire life safety passed final inspection.
|
FIR07-00344
| INSP-Sprinkler Rough-in/Hydro | 8/3/2007 | 8/6/2007 | 8/6/2007 12:57:53 PM | A | FAIL |
|
|
Field installation is not consistent with approved plans regarding main locations, pipe size, branch line routing, some head locations, etc. Per review notes, any variance affecting these components of the system will requrie plan resubmittals due to narrow calc. margins. Approved plans must match field install prior to request for field inspection, as-builts will not be accepted in this situation.
|
FIR07-00267
| INSP-Final Inspection | 8/2/2007 | 8/6/2007 | 8/6/2007 12:41:02 PM | A | PART |
|
|
Final pending repair or replacement of one strobe only device at the waiting area which failed to fully function during testing, location indicated on approved plans, remainder of FA work tested okay.
|
FIR07-00526
| INSP-Sprinkler Rough-in/Hydro | 8/3/2007 | 8/6/2007 | 8/6/2007 12:38:05 PM | A | PASS |
|
|
OH hydrostatic test completed, inspection passed.
|