Inspections for the day of: Monday, August 6, 2007.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-03378 FIRE-Final Inspection8/5/20078/6/20078/7/2007 11:49:23 AMPFAIL
The keyed locks on the north and south exit doors need to be removed.
FIR07-00459 INSP-Sprinkler Rough-in8/6/20078/6/20078/6/2007 5:13:01 PMPPART
The inspection for today was for the hot tap and 20'-0 of pipe from the hot tap. This piping is ok to cover.
FIR07-00477 INSP-Sprinkler Rough-in8/6/20078/6/20078/6/2007 5:10:46 PMPFAIL
I inspected the two bays over the mezzanine and found that the hangers and trapeze members are the wrong size. This is the only area I inspected.
FIR07-00497 INSP-Sprinkler Rough-in/Hydro8/3/20078/6/20078/6/2007 2:30:43 PMPPASS
See the city approved plans for the locations where the sprinkler piping can be covered. The long branchline located along the north side of the building is now sized at all 2" with a bunch of new pendants. I told Russ that this will have to be resubmitted. This area is not approved for cover especially since there is exposed wood above the ceilings. Per the general contractor the wood will be covered.
FIR05-00536 INSP-Sprinkler Rough-in8/3/20078/6/20078/6/2007 1:21:21 PMAPASS
See the city approved plans for the locations where sprinkler piping can be covered on the second and fourth floors.
BLD07-01743 FIRE-Final Inspection8/3/20078/6/20078/6/2007 12:31:36 PMAPASS
Life safety passed.
BLD07-00135 FIRE-Final Inspection8/3/20078/6/20078/6/2007 10:39:05 AMAPASS
life safety passed
BLD07-00353 FIRE-Final Inspection8/3/20078/6/20078/6/2007 9:09:09 AMAFAIL
This tenant has been occupied so I posted a "Do Not Occupy" sticker on the main entrance door and told the manager that they need to leave after he stated that they did not have their certificate of occupancy. The fire sprinkler permit could not be finaled because no plans were on site and nearly all of the ceiling tile had been installed. Also per the mechanical plans duct smoke detectors are to be installed yet there is no fire alarm permit. Fire extinguishers are also missing. Basically no inspections have been performed.
FIR07-00535 INSP-Sprinkler Rough-in/Hydro8/3/20078/6/20078/6/2007 9:06:11 AMAFAIL
No approved plans on site and the ceiling tile has been installed.
FIR07-00219 FIR-Aging Inspection8/6/20078/6/20078/6/2007 8:13:15 AM NR
work is in progress