BLD06-03378
| FIRE-Final Inspection | 8/5/2007 | 8/6/2007 | 8/7/2007 11:49:23 AM | P | FAIL |
|
|
The keyed locks on the north and south exit doors need to be removed.
|
FIR07-00459
| INSP-Sprinkler Rough-in | 8/6/2007 | 8/6/2007 | 8/6/2007 5:13:01 PM | P | PART |
|
|
The inspection for today was for the hot tap and 20'-0 of pipe from the hot tap. This piping is ok to cover.
|
FIR07-00477
| INSP-Sprinkler Rough-in | 8/6/2007 | 8/6/2007 | 8/6/2007 5:10:46 PM | P | FAIL |
|
|
I inspected the two bays over the mezzanine and found that the hangers and trapeze members are the wrong size. This is the only area I inspected.
|
FIR07-00497
| INSP-Sprinkler Rough-in/Hydro | 8/3/2007 | 8/6/2007 | 8/6/2007 2:30:43 PM | P | PASS |
|
|
See the city approved plans for the locations where the sprinkler piping can be covered. The long branchline located along the north side of the building is now sized at all 2" with a bunch of new pendants. I told Russ that this will have to be resubmitted. This area is not approved for cover especially since there is exposed wood above the ceilings. Per the general contractor the wood will be covered.
|
FIR05-00536
| INSP-Sprinkler Rough-in | 8/3/2007 | 8/6/2007 | 8/6/2007 1:21:21 PM | A | PASS |
|
|
See the city approved plans for the locations where sprinkler piping can be covered on the second and fourth floors.
|
BLD07-01743
| FIRE-Final Inspection | 8/3/2007 | 8/6/2007 | 8/6/2007 12:31:36 PM | A | PASS |
|
|
Life safety passed.
|
BLD07-00135
| FIRE-Final Inspection | 8/3/2007 | 8/6/2007 | 8/6/2007 10:39:05 AM | A | PASS |
|
|
life safety passed
|
BLD07-00353
| FIRE-Final Inspection | 8/3/2007 | 8/6/2007 | 8/6/2007 9:09:09 AM | A | FAIL |
|
|
This tenant has been occupied so I posted a "Do Not Occupy" sticker on the main entrance door and told the manager that they need to leave after he stated that they did not have their certificate of occupancy. The fire sprinkler permit could not be finaled because no plans were on site and nearly all of the ceiling tile had been installed. Also per the mechanical plans duct smoke detectors are to be installed yet there is no fire alarm permit. Fire extinguishers are also missing. Basically no inspections have been performed.
|
FIR07-00535
| INSP-Sprinkler Rough-in/Hydro | 8/3/2007 | 8/6/2007 | 8/6/2007 9:06:11 AM | A | FAIL |
|
|
No approved plans on site and the ceiling tile has been installed.
|
FIR07-00219
| FIR-Aging Inspection | 8/6/2007 | 8/6/2007 | 8/6/2007 8:13:15 AM | | NR |
|
|
work is in progress
|