Inspections for the day of: Wednesday, August 6, 2008.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00454 INSP-Sprinkler Rough-in8/5/20088/6/20088/7/2008 4:13:40 PMPFAIL
See the city approved plans for locations of deficiencies which include tenting issues, missing pendant and the garage sidewalls appear to be too low.
FIR07-00213 INSP-Final Inspection8/5/20088/6/20088/6/2008 4:23:19 PMPCANC
Per Jim Danes the replacement sprinkler canopies are on order. The inspection will be called in at a later time.
BLD08-00829 FIRE-Final Inspection8/6/20088/6/20088/6/2008 4:04:38 PMPPASS
fire life safety passed
FIR08-00413 INSP-Sprinkler Rough-in/Hydro8/5/20088/6/20088/6/2008 12:47:16 PMAPASS
The remaining second floor rooms at the elevator are ok to cover.
FIR08-00413 INSP-Final Inspection8/5/20088/6/20088/6/2008 12:46:04 PMAFAIL
Project is not ready for final inspection
FIR08-00395 INSP-Final Inspection8/5/20088/6/20088/6/2008 12:45:17 PMAPASS
permit finaled
BLD08-01662 FIRE-Final Inspection8/5/20088/6/20088/6/2008 11:24:38 AMAPASS
Life safety passed
BLD08-00921 FIRE-Final Inspection8/5/20088/6/20088/6/2008 11:17:04 AMAFAIL
The shell building permit needs finaled prior to this permit being finaled. Per Sam Rogers we do not need to reverify the elevator recall since it has been approved by the State of Idaho elevator inspector but the Area of Refuge still needs inspected. Those two items are required for the shell. Items found wrong on the tenant improvement include: Suite number needs to be provided, repair all of the exit signs and emergency lights as marked on sheet E1.0 and either install the duct dectors as discussed or remove them since they are not shown on the drawings and both units are less than 2,000 cfm and mount the fire extinguisher.
FIR08-00501 INSP-Final Inspection8/4/20088/6/20088/6/2008 9:00:26 AMAPASS
Permit finaled
FIR08-00502 INSP-Final Inspection8/4/20088/6/20088/6/2008 8:59:25 AMAFAIL
There was no access to the building. No inspection was performed.