FIR09-00284
| FIR-Aging Inspection | 8/6/2009 | 8/6/2009 | 8/6/2009 3:56:44 PM | | DONE |
|
|
Site work in progress.
|
FIR09-00290
| INSP-Final Inspection | 8/6/2009 | 8/6/2009 | 8/6/2009 3:56:04 PM | P | PART |
|
|
Retest of correction notice items at the main office area only completed okay. Remaining issue for this area includes relays for mag locks at secured doors not yet installed for interconnection to the fire alarm system.
|
FIR09-00103
| INSP-Final Inspection | 8/6/2009 | 8/6/2009 | 8/6/2009 3:52:31 PM | P | PASS |
|
|
Fire alarm permit is approved for final status as necessary corrections have been finished in the common exit corridors per agreement.
|
BLD08-02498
| FIRE-Final Inspection | 8/6/2009 | 8/6/2009 | 8/6/2009 3:50:25 PM | P | FAIL |
|
|
The existing building fire sprinkler system is overdue annual inspection per the most recent riser tag dated 2006.
|
FIR09-00401
| INSP-Final Inspection | 8/5/2009 | 8/6/2009 | 8/6/2009 3:48:19 PM | A | PASS |
|
|
Scope of fire alarm system upgrade work passed field testing, permit final approved.
|
FIR09-00033
| INSP-Sprinkler Rough-in/Hydro | 8/4/2009 | 8/6/2009 | 8/6/2009 3:47:17 PM | P | PART |
|
|
Overhead rough-in inspection for system #15 passed-see dated initials on plans.
|
FIR09-00033
| INSP-Sprinkler Rough-in/Hydro | 8/4/2009 | 8/6/2009 | 8/6/2009 3:45:45 PM | A | PART |
|
|
Concluded satisfactory 24 hr. pneumatic retest of the overhead preaction systems #26,27,28 and 29.
|
BLD09-01187
| FIRE-Final Inspection | 8/5/2009 | 8/6/2009 | 8/6/2009 12:34:18 PM | A | PASS |
|
|
Fire life safety passed, contractor to repair existing non-required exit sign as discussed prior to structural inspection.
|
BLD08-02517
| FIRE-Final Inspection | 8/6/2009 | 8/6/2009 | 8/6/2009 12:23:53 PM | P | PASS |
|
|
Final fire life safety inspection passed.
|