Inspections for the day of: Friday, August 6, 2010.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00088 FIR-Aging Inspection8/6/20108/6/20108/10/2010 2:08:29 PM FAIL
FIR10-00207 FIR-Aging Inspection8/6/20108/6/20108/10/2010 2:05:25 PM DONE
BLD10-00992 FIRE-Final Inspection8/5/20108/6/20108/6/2010 3:46:32 PMAFAIL
Provide approved door hardware at 105B, post tactile exit sign per plan notes #18, scope of work at the 1st floor is incomplete-discussed possible plan modification with contractor.
BLD10-01326 FIRE-Final Inspection8/5/20108/6/20108/6/2010 3:43:35 PMPPASS
Fire life safety passed inspection.
FIR10-00333 INSP-Final Inspection8/6/20108/6/20108/6/2010 3:43:00 PMPPASS
Corrections field verified, fire sprinkler permit final approved.
FIR10-00381 INSP-Final Inspection8/5/20108/6/20108/6/2010 3:34:09 PMPPASS
Inspection passed, fire alarm permit finaled.
BLD10-00831 FIRE-Final Inspection8/6/20108/6/20108/6/2010 1:26:43 PMPFAIL
Corrections items include; repair one exit sign, one EM light and provide directional arrow at one exit sign per plan on the third floor. Repair one exit/EM light at the second floor. Scope of work per the permit description for the new exit discharge at the ground floor SW corner has not been done, item #15 per the fire code review is not yet provided.
BLD10-00288 FIRE-Final Inspection8/6/20108/6/20108/6/2010 1:12:48 PMANR
Pending project related fire alarm permit FIR10-00293 and note #4 per fire code review comments.
BLD10-00960 FIRE-Final Inspection8/6/20108/6/20108/6/2010 1:11:01 PMPPASS
Fire life safety inspection completed acceptable.
FIR10-00294 INSP-Final Inspection8/6/20108/6/20108/6/2010 1:08:39 PMPPASS
Corrections finished, reinspection passed. Tenant fire alarm permit final approved.
FIR10-00293 INSP-Final Inspection8/6/20108/6/20108/6/2010 1:06:30 PMPNR
No test performed due to non-functional elevator.
FIR10-00295 INSP-Final Inspection8/6/20108/6/20108/6/2010 1:04:25 PMPPASS
Remainder of the scope of work and C/N items finished while on site and verified for completion. Fire sprinkler permit finaled.
FIR10-00290 INSP-Final Inspection8/6/20108/6/20108/6/2010 1:02:30 PMPPASS
Re-inspection for correction items passed, dry system pressure switch reset repaired by sprinkler contractor, fire alarm permit final okayed.
FIR10-00295 INSP-Sprinkler Rough-in/Hydro8/5/20108/6/20108/6/2010 12:58:49 PMAPART
Reinspection for previous correction items completed acceptable. However, noted fire sprinkler work at the third floor per plan had not been done, also missing an escutcheon at the first floor lobby.
FIR10-00006 INSP-Alarm Testing7/14/20108/6/20108/6/2010 12:00:00 AMACANC